OPERATING SEQUENCE

Base Unit Controls

INDOOR (SUPPLY) FAN

If the thermostat fan operation is selected as Continuous,
then the indoor (supply) fan motor, which is remotely locat-
ed in the fan coil, runs continuously. If the thermostat fan op-
eration is selected as Automatic, then the indoor (supply)
fan motor runs when there is a call for Ventilation, Cooling,
or Heating. When thermostat is satisfied, then the indoor
(supply) fan motor stops. If there is a fan fault or a shutdown
condition in the fan coil, then the indoor (supply) fan will not
run if there is a call for ventilation, cooling, or heating and
the CHS unit will act as if it is not receiving a thermostat
demand.
COOLING,
UNIT
WITHOUT
TWO-STAGE UNITS
For two stage units, the CHS072*G/H and CHS091*M/N
use a two-stage Copeland
1. Third-party trademarks and logos are the property of their respective
owners.
CHS-072-121-01SI
10 Ton Heat Pump Dual Stage Charging Chart R-410A
(compressor full load, all condenser fans operating)
Fig. 17 — CHS121*G/H Charging Chart
ECONOMIZER
™1
Ultratech Scroll compressor in
Specifications subject to change without notice.
PN: 38AU000486 REV -
conjunction with a two-stage Comfort Alert Module (CADM).
The CHS121*G/H uses two compressors in tandem on a
single circuit in conjunction with two single-stage Comfort
Alert Modules (CADM).
CHS072*G/H and CHS091*M/N
When thermostat calls for Stage 1 Cooling, terminal Y1 is
energized. The CHS unit's Defrost Board (DFB) receives
this input at P2-5. DFB issues 24-v outputs at OF, P3-7
(RVS1) and P3-10 (COMP1). The OF output energizes out-
door fan relay (OFR); both outdoor fan motors start and run.
The output RVS1 energizes the reversing valve solenoid
(RVS); Reversing valve switches to Cooling position. Output
PL3-10 (COMP1, 24-v) is received at CADM terminal Y. If
anti-recycle time delay period has not expired, safety pres-
sure switches are open, and/or lockout alarms are active,
CADM relay will remain open, preventing compressor start.
When safety pressure switches are closed and CADM time
delay expires, the CADM relay closes, energizing Solenoid
Valve Relay SVR and compressor contactor C. SVR con-
tacts close, energizing the external liquid line solenoid
valve. Solenoid valve LLSV opens. Compressor contactor C
closes, energizing the compressor motor. Compressor
starts and system runs in Stage 1 Cooling mode.