Compressor Rotation; Operating Sequence; Room-Mounted Thermostat - Carrier Omnizone 50XCA06 Installation, Start-Up And Service Instructions Manual

Air-cooled indoor self contained systems
Hide thumbs Also See for Omnizone 50XCA06:
Table of Contents

Advertisement

CFM
0.00
0.10
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
6,000
558
1.77
619
6,300
585
1.95
644
6,600
613
2.14
669
6,900
641
2.34
695
7,200
669
2.55
721
7,500
697
2.77
747
7,800
725
2.99
773
8,000
743
3.15
790
8,300
771
3.39
817
8,600
799
3.64
843
8,900
827
3.90
869
9,200
855
4.16
896
9,500
883
4.44
923
9,800
911
4.72
949
10,000
929
4.92
967
CFM
1.00
1.10
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
6,000
1030 4.12 1067 4.46 1102 4.80 1137 5.14 1171 5.49 1203 5.84 1235 6.20 1267 6.56 1297 6.92 1327 7.29
6,300
1044 4.42 1080 4.76 1116 5.12 1150 5.47 1183 5.83 1215 6.20 1247 6.56 1278 6.94 1308 7.31
6,600
1059 4.73 1095 5.09 1129 5.45 1163 5.82 1196 6.19 1228 6.57 1259 6.95 1289 7.33
6,900
1075 5.06 1110 5.43 1144 5.81 1177 6.18 1209 6.57 1241 6.96 1272 7.35
7,200
1091 5.41 1125 5.79 1159 6.18 1191 6.57 1223 6.97 1254 7.36
7,500
1108 5.78 1141 6.18 1174 6.57 1206 6.98 1238 7.38
7,800
1125 6.17 1158 6.58 1190 6.99 1222 7.40
8,000
1137 6.45 1169 6.86 1201 7.28
8,300
1154 6.88 1187 7.30
8,600
1173 7.33
8,900
9,200
9,500
9,800
10,000
LEGEND
Bhp — Brake Horsepower
ESP — External Static Pressure

Compressor Rotation

To determine whether or not compressor is rotating in the proper
direction:
1.
Connect service gages to suction and discharge pressure
fittings.
2.
Energize the compressor.
3.
The suction pressure should drop and the discharge pressure
should rise, as is normal on any start-up.
4.
If the suction pressure does not drop and the discharge pres-
sure does not rise to normal levels, the compressor may be
rotating in the wrong direction.
5.
Since the compressor and fan motors are connected in phase
during production, it is likely that the evaporator and con-
denser fans are probably also rotating in the wrong direction.
6.
Turn off power to the unit and lock and tag disconnect per
standard safety procedures.
7.
Reverse any two of the unit power leads.
Table 15 — Evaporator Fan Performance — 50XCA24 Units
0.20
0.30
1.99
675 2.19
728 2.39
2.17
698 2.38
749 2.58
2.36
722 2.57
771 2.77
2.56
746 2.77
793 2.97
2.77
770 2.98
816 3.18
2.99
794 3.20
839 3.40
3.21
818 3.43
862 3.63
3.37
835 3.58
878 3.79
3.61
860 3.82
901 4.03
3.86
885 4.07
925 4.28
4.12
910 4.33
949 4.54
4.38
935 4.60
973 4.81
4.66
961 4.88
998 5.09
4.95
987 5.16
1023 5.37
5.14
1004 5.36
1039 5.57
1.20
1.30
ESP (in. wg)
0.40
0.50
777 2.58
824 2.76
869 2.94
797 2.77
843 2.95
887 3.13
818 2.96
862 3.15
905 3.33
839 3.17
882 3.36
923 3.54
860 3.38
902 3.57
943 3.76
882 3.60
923 3.79
962 3.98
904 3.83
944 4.03
982 4.22
918 3.99
958 4.18
996 4.38
941 4.23
979 4.43
1017 4.62
964 4.48
1001 4.68
1038 4.88
987 4.75
1024 4.95
1059 5.14
1010 5.02
1046 5.22
1081 5.41
1034 5.29
1069 5.50
1103 5.69
1058 5.58
1092 5.78
1125 5.98
1074 5.78
1107 5.98
1140 6.18
ESP (in. wg)
1.40
1.50
NOTES:
1. Units are available with several motor hp options. Refer to Table 1.
2. Static pressure losses for any options or accessories must be
applied to external static pressure before entering the fan perfor-
mance table.
3. Interpolation is permitted; extrapolation is not.
4. Fan performance is based on 1 in. standard throwaway filter, unit
casing, and wet DX (direct expansion) coil losses at sea level.
8.
Remove lock and tag per standard safety procedures and
reapply power to the unit.
9.
The suction and discharge pressure levels should now move
to their normal start-up levels.
NOTE: When the compressor is rotating in the wrong direction,
the unit makes an elevated level of noise and does not provide
cooling.

Operating Sequence

All units require the addition of a thermostat accessory package to
complete the control circuit. The sequence of operation may vary
depending on which package is selected.

ROOM-MOUNTED THERMOSTAT

These units use an electronic thermostat mounted in the condi-
tioned space.
32
0.60
0.70
0.80
912 3.11
952 3.28
928 3.31
968 3.48
945 3.51
985 3.68
963 3.72
1002 3.90
982 3.94
1019 4.12
1000 4.17
1037 4.35
1020 4.40
1056 4.58
1033 4.56
1068 4.75
1053 4.81
1087 5.00
1073 5.07
1107 5.26
1093 5.33
1127 5.52
1114 5.61
1147 5.80
1136 5.89
1168 6.08
1157 6.18
1189 6.37
1172 6.38
1203 6.57
1.60
1.70
1.80
0.90
992 3.44
1007 3.64
1023 3.85
1039 4.07
1056 4.29
1073 4.52
1091 4.76
1103 4.93
1121 5.18
1140 5.44
1160 5.71
1179 5.99
1199 6.27
1220 6.57
1233 6.77