28 Installation
3.7.
Connecting the control signals
For all applications with conventional controllers ( such as NT6C25BA or
NT6C25BB ) or front access controllers ( NT6C25FA ), execute the steps
contained in Procedure 7 to connect the NT5C05CC rectifier ( see Figure
9 ).
Procedure 7 - Connecting the NT5C05CC to the controller
Step
1
2
Figure 9 - Typical connections between rectifiers and the conventional
Rectifier
Rectifier
Rectifier
Rectifier
Rectifier
Rectifier
NT6C43PB
MONITOR
Cables P0736355
UM5C05C P0745680 Standard 6.00 October 2001
Connect each rectifier to the NT6C43PB board ( positions J1 to J6 ),
located at the top front of the cabinet or frame, with P0747000
cables.
Connect the NT6C43PB board ( positions J7 to J12 ) to the
controller with P0736355 cables for conventional controllers ;
and with P0736268 cables for front access controllers.
controller
# 6
# 5
# 4
# 3
# 2
# 1
Action
end
Cables P0747000
J13
J1
J2
J7
J8
CONTROLLER NT
(NT6C25BA or NT6C25BB)
J3
J4
J5
J9
J10
J11
Emerson Energy Systems
J6
J12