Mechanical And Electrical Specifications Of A 1200 A Cabinet; Ambient Conditions Of A 1200 A Cabinet; Table 5 - Mechanical Specifications Of The Nt6C43Cb 1200 A Cabinet; Table 6 - Electrical Specifications Of The Nt6C43Cb - Emerson 200I/48-NT5C05C Installation And User Manual

Helios modular switch mode rectifier 200i/48
Table of Contents

Advertisement

16 Specifications
2.3.

Mechanical and electrical specifications of a 1200 A cabinet

Table 5 - Mechanical specifications of the NT6C43CB 1200 A cabinet

Height :
Depth :
Width :
Table 6 - Electrical specifications of the NT6C43CB 1200 A cabinet
Input voltage :
Output voltage :
Output current :
2.4.

Ambient conditions of a 1200 A cabinet

Table 7 — Ambient conditions for the NT6C43CB 1200 A cabinet
Operating
conditions
Storage conditions
UM5C05C P0745680 Standard 6.00 October 2001
84.00 inches ( 213.36 cm )
23.63 inches ( 60.0 cm )
23.63 inches ( 60.0 cm )
380 / 415 V ac three phase
–46 V dc to –58 V dc
1200 A
The cabinet is designed for use under the following
ambient conditions.
Temperature:
0°C to 50°C ( 32°F to 122°F )
0° to 40°C ( 32° to 104°F ) with air
filters
Humidity:
0 to 95% RH ( non-condensing )
Altitude:
sea level to 7,000 ft ( 2,100 m )
During transportation and storage, the acceptable
ambient conditions are :
Temperature:
–55°C ( –67°F )
+60°C ( 140°F ) dry heat
Humidity:
0 to 95% RH ( non-condensing )
Emerson Energy Systems

Advertisement