Procedure 6 - Connecting the ac male plug between the NT5C05CC rectifier
Step
1
2
3
4
5
6
Figure 8 - Connecting ac to the rectifier NT5C05CC
TB1
L1 L2 L3
GRD
Emerson Energy Systems
and the ac female plug in a 1200 A cabinet
Install the ac breaker ( 30 A / 3 phases per rectifier ) in the 380 /
415 volts ac service panel.
Put the ac breaker for the NT5C05CC rectifier, located in the ac
service panel, to OFF.
Run the metric no. 25 ( 10 AWG ) ac supply cable ( 3 conductors
and ground ) to the female receptacle ( see Figure 8 ). Connect the
female connector to the male connector.
Run the signal cable from the rectifier to the interconnect board or
controller as specified in the " Connecting the control signals "
section.
Secure the signal cables to the insulating busbar support, located in
the cabinet, with cable ties.
Start-up the rectifier as described in the " Start-up " section.
CONNECTION
R1 (TB1-L1)
S2 (TB1-L2)
T3 (TB1-L3)
GREEN / YELLOW
Rectifier 200I/48 NT5C05C Installation and User Manual
Action
end
A
A
BROWN
BLUE
WIRE COLOR
BLUE
BROWN
BLACK
GREEN/YELLOW
FEMALE CONNECTOR
Installation 27
BLACK
SECT A-A