Emerson Rosemount 2130 Reference Manual

Emerson Rosemount 2130 Reference Manual

Level switch vibrating fork
Hide thumbs Also See for Rosemount 2130:

Advertisement

Quick Links

Reference Manual
00809-0100-4130, Rev EA
May 2022
Rosemount
2130 Level Switch
Vibrating Fork

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Rosemount 2130 and is the answer not in the manual?

Questions and answers

Summary of Contents for Emerson Rosemount 2130

  • Page 1 Reference Manual 00809-0100-4130, Rev EA May 2022 ™ Rosemount 2130 Level Switch Vibrating Fork...
  • Page 2 • 1-800-654-7768 (24 hours a day — includes Canada) • Outside of these areas, contact your local Emerson representative. WARNING Failure to follow safe installation and servicing guidelines could result in death or serious injury. Ensure the level switch is installed by qualified personnel and in accordance with applicable code of practice.
  • Page 3 Equipment ratings and certifications are no longer valid on any products that have been damaged or modified without the prior written permission of Emerson. Any continued use of product that has been damaged or modified without the written authorization is at the customer’s sole risk and expense.
  • Page 5: Table Of Contents

    6.6 Spare parts..........................60 6.7 Replacement and calibration of cassettes.................. 60 6.8 Opening the lid (cover)......................62 6.9 Service support..........................63 Appendix A Specifications and reference data................65 A.1 General............................65 A.2 Physical specifications....................... 65 A.3 Performance specifications......................66 Rosemount 2130 Level Switch...
  • Page 6 Contents Reference Manual May 2022 00809-0100-4130 A.4 Electrical specifications......................67 A.5 Functional specifications......................68 A.6 Environmental specifications.....................68 A.7 Dimensional drawings....................... 70 Reference Manual...
  • Page 7: Chapter 1 Introduction

    Introduction Using this manual The sections in this manual provide detailed information on installing, operating, and maintaining the Rosemount 2130 Level Switch - Vibrating Fork. The sections are organized as follows: Level switch overview provides a description of the level switch and its basic principles.
  • Page 8 Introduction Reference Manual May 2022 00809-0100-4130 Reference Manual...
  • Page 9: Level Switch Overview

    Process characteristics Emerson's vibrating fork technology is virtually unaffected by turbulence, foam, solids content, coating products, and liquid properties. The natural frequency (1400 Hz) of the fork avoids interference from plant vibration that may cause false switching to a wet state.
  • Page 10: Application Examples

    Spillage caused by overfilling can be hazardous to people and the environment, resulting in lost product and potentially high clean-up costs. The Rosemount 2130 is an overfill prevention product from Emerson that can be used as one of multiple layers of protection.
  • Page 11 By selecting the option of direct load switching or relay electronics, the Rosemount 2130 is ideal for reliable pump control and can be used to protect against pumps running dry.
  • Page 12: Components Of The Level Switch

    Hygienic applications With the highly polished forks option providing a surface finish (Ra) better than 0.4 μm, the Rosemount 2130 meets the most stringent hygienic requirements used in food and beverage, and pharmaceutical applications. The Rosemount 2130 is robust enough to easily withstand CIP (Clean-In- Place) and SIP (Steam-In-Place) cleaning routines.
  • Page 13 2.5.2 Fork design The “fast drip” design allows the liquid to be quickly drawn away from the fork tip, making the Rosemount 2130 quicker and more responsive in high density or viscous liquid applications. Figure 2-2: “Fast drip” forks 2.5.3...
  • Page 14 Magnetic test point A magnetic test point is located on the side of the housing, allowing a functional test of the Rosemount 2130 and a system connected to it. Holding a magnet to the test point causes the output to change state.
  • Page 15: Chapter 3 Mechanical Installation

    In explosion-proof/flameproof and non-incendive installations, do not remove the housing cover when power is applied to the level switch. The housing cover must be fully engaged to meet flameproof/explosion-proof requirements. Rosemount 2130 Level Switch...
  • Page 16: Installation Considerations

    Before installing the level switch, review the safety, environmental, application, and pre- installation sections. 3.2.1 Environmental considerations The Rosemount 2130 is weatherproof and protected against the ingress of dust, but must be protected from flooding. Avoid installing the level switch near heat sources. Reference Manual...
  • Page 17 Figure 3-1: Environmental Considerations 3.2.2 Application considerations The Rosemount 2130 is a wired point-level device for use on open or closed vessels (tanks) and in pipework containing liquid mediums. For most liquids, including coating, aerated liquids and slurries, the function is virtually unaffected by flow, turbulence, bubbles, foam, vibration, solid particles, build-up, or properties of the liquid medium.
  • Page 18 Emerson. Foams In almost all cases, the Rosemount 2130 is insensitive to foams (i.e. does not see the foam). However in rare occasions, some very dense foams may be seen as liquid; known examples of this are found in ice-cream and orange juice manufacturing.
  • Page 19 37 lb. (18 kg). A risk assessment is required to be done before carrying, lifting, and installing the level switch. Use both hands to carry the extended length and high temperature versions, and do not hold a level switch by the forks (see Figure 3-4). Rosemount 2130 Level Switch...
  • Page 20 Ensure a proper seal by installing the electronics housing cover so that metal contacts metal. Always use Emerson's O-rings. Mounting orientation Mount the Rosemount 2130 at any angle that allows the level of the process medium to rise, fall, or flow through the fork gap. Reference Manual...
  • Page 21 2130***E 2130***M 2130***E A. 2.1 in. (55 mm) ® B. ROCKWOOL surrounds the Rosemount 2130 C. 3.9 in. (100 mm) clearance all around D. 5.9 in. (150 mm) E. ROCKWOOL Pipe installation requirements • The inside pipe diameter (D) must be 1.4 in. (35 mm) or larger.
  • Page 22 Mechanical installation Reference Manual May 2022 00809-0100-4130 Other recommendations • Always install in the normally “on” state. — High-level alarm: recommended Mode setting is Dry = on. Low-level alarm: recommended Mode setting is Wet = on. — • Avoid: — Installing near to liquid entering the tank at the filling-point.
  • Page 23 Figure 3-9: Vertical Installation (Marine GL Approved) A. Maximum 1.3 ft. (0.4 m) B. 2.3 ft. (0.7 m) C. 0.65 ft. (0.2 m) Figure 3-10: Horizontal Installation (Standard) A. Maximum 3.28 ft. (1.0 m) B. 3.28 ft. (1.0 m) Rosemount 2130 Level Switch...
  • Page 24 Mechanical installation Reference Manual May 2022 00809-0100-4130 Figure 3-11: Horizontal Installation (Marine GL Approved) A. Maximum 1.3 ft. (0.4 m) B. 2.3 ft. (0.7 m) C. 0.65 ft. (0.2 m) Reference Manual...
  • Page 25: Installation Procedures

    The fork is correctly aligned by positioning the groove or notch as indicated (Figure 3-13). Figure 3-13: Correct Fork Alignment for Vessel (Tank) Installation A. Tri Clamp process connections have a circular notch B. Threaded process connections have a groove C. Flanged process connections have a circular notch Rosemount 2130 Level Switch...
  • Page 26 Mechanical installation Reference Manual May 2022 00809-0100-4130 Fork alignment in a pipe installation The fork is correctly aligned by positioning the groove or notch as indicated (Figure 3-14). Figure 3-14: Correct Fork Alignment for Pipe Installation A. Tri Clamp process connections have a circular notch B.
  • Page 27 A. Gasket for BSPP (G) threaded connection Figure 3-16: Horizontal Installation A. Gasket for BSPP (G) threaded connection Threaded flange connection Procedure 1. Place the customer-supplied flange and gasket on the vessel (tank) nozzle. A. Gasket (customer supplied) Rosemount 2130 Level Switch...
  • Page 28 Mechanical installation Reference Manual May 2022 00809-0100-4130 2. Tighten the bolts and nuts with sufficient torque for the flange and gasket. 3. Seal and protect the threads. Use anti-seize paste or PTFE tape according to site procedures. A gasket may be used as a sealant for BSPP (G) threaded connections. 4.
  • Page 29 Mechanical installation 00809-0100-4130 May 2022 3.3.4 Mounting the flanged version Procedure 1. Lower the level switch into the nozzle. A. Gasket (customer supplied) 2. Tighten the bolts and nuts with sufficient torque for the flange and gasket. Rosemount 2130 Level Switch...
  • Page 30 Mechanical installation Reference Manual May 2022 00809-0100-4130 3.3.5 Mounting the Tri Clamp version Procedure 1. Lower the level switch into the flange face. A. Seal (supplied with Tri Clamp) 2. Fit the Tri Clamp. Reference Manual...
  • Page 31: Chapter 4 Electrical Installation

    In explosion-proof/flameproof and non-incendive installations, do not remove the housing cover when power is applied to the level switch. The housing cover must be fully engaged to meet flameproof/explosion-proof requirements. Rosemount 2130 Level Switch...
  • Page 32: Prepare The Electrical Connections

    Electrical installation Reference Manual May 2022 00809-0100-4130 WARNING Electrical shock could cause death or serious injury. Avoid contact with the leads and terminals. High voltage that may be present on leads can cause electrical shock. Ensure the power to the level switch is off, and the lines to any other external power source are disconnected or not powered while wiring the level switch.
  • Page 33 Before use, check the cable glands and blanking plugs are suitably rated. • Isolate supply before connecting the switch or removing the electronics. • The Protective Earth (PE) terminal must be connected to an external earthing system. Note When replacing a cassette, it is important to re-calibrate. Rosemount 2130 Level Switch...
  • Page 34 The Rosemount 2130 requires a minimum current to operate (I ), which continues to flow when the output is ‘off’. If selecting a relay to wire in series with the Rosemount 2130, ensure the drop-out voltage of the relay is greater than the voltage generated across the relay coil when I flows through it.
  • Page 35 Mode: wet on, low level alarm < 4 mA < 4 mA 12 V 12 V DPST DPST DPST DPST LED on continuously LED flashes every second LED on continuously LED flashes every second = Load on = Load off Rosemount 2130 Level Switch...
  • Page 36 Electrical installation Reference Manual May 2022 00809-0100-4130 PNP/PLC cassette Figure 4-2: PNP/PLC (3-wire) Cassette (Yellow Label) – Code P Wet On Mode O/P 0V F = Fuse 2A(T) Table 4-3: Electrical Parameters Parameter Value 20 - 60 Vdc < 4 mA + I <...
  • Page 37 <100 μA <100 μA < 3 V < 3 V PNP dc < 3 V < 3 V <100 μA <100 μA LED on continuously LED flashes every second LED on continuously LED flashes every second Rosemount 2130 Level Switch...
  • Page 38 Electrical installation Reference Manual May 2022 00809-0100-4130 Relay DPCO cassette (standard version) Figure 4-3: Relay DPCO Cassette, Standard Version (Green Label) – Code D OPERATION MODE Warning Isolate Supply Before Removing Seconds Delay Dry On Dr y On Wet On Wet On Fuse 0.5 (T) DPST...
  • Page 39 NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO LED on continuously LED flashes every second LED on continuously LED flashes every second Rosemount 2130 Level Switch...
  • Page 40 Electrical installation Reference Manual May 2022 00809-0100-4130 Fault and alarm relays (2 x SPCO) cassette Figure 4-4: Fault and Alarm Relay Outputs Cassette (Light Green Label) – Code D with Option R2264 Fuse 0.5 (T) DPST Live Note A Double Pole, Single Throw on/off switch must be fitted for safe disconnection of the power supply.
  • Page 41 NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO NC C NO LED on continuously LED flashes every second LED on continuously LED flashes every second Rosemount 2130 Level Switch...
  • Page 42 Figure 4-5: NAMUR Cassette (Light Blue Label) – Code N A. A certified intrinsically safe isolating amplifier to IEC 60947-5-6 Note • This cassette is suitable for Intrinsically Safe (IS) applications and requires a certified isolating barrier. See the Rosemount 2130 Product Certifications document for Intrinsically Safe approvals. •...
  • Page 43 Mode: dry on, high level alarm Mode: wet on, low level alarm > 2.2 mA < 1.0 mA > 2.2 mA < 1.0 mA LED on continuously LED flashes every second LED on continuously LED flashes every second Rosemount 2130 Level Switch...
  • Page 44 Figure 4-6: 8/16 mA Cassette (Dark Blue Label) – Code M A. A certified intrinsically safe isolating amplifier to IEC 60947-5-6 Note • This cassette is suitable for Intrinsically Safe (IS) applications and requires a certified isolating barrier. See the Rosemount 2130 Product Certifications document for Intrinsically Safe approvals. •...
  • Page 45 Mode: dry on, high level alarm Mode: wet on, low level alarm > 15 mA < 8.5 mA > 15 mA < 8.5 mA LED on continuously LED flashes every second LED on continuously LED flashes every second Rosemount 2130 Level Switch...
  • Page 46 Electrical installation Reference Manual May 2022 00809-0100-4130 Fault condition detection (self-check mode only) When a fault condition is detected in the self-check operating mode, the heartbeat LED flashes once every half a second and every third flash is missed. The output from the level switch will then be as Table 4-15.
  • Page 47: Connect Wiring And Power Up

    Housings with NPT conduit entries do not have an earth ground point and must use the fork earth. Figure 4-8: Ground Screws A. External ground screw Connect wiring and power up Procedure Verify the power supply is disconnected. Rosemount 2130 Level Switch...
  • Page 48 In an explosion-proof/flameproof installation, do not remove the level switch cover when power is applied to the unit. The cover must also not to be removed in extreme environmental conditions. Versions of the Rosemount 2130 with explosion-proof/flameproof approvals have a cover-lock to be undone first. 3. Remove the plastic plugs.
  • Page 49 Apply PTFE tape or other sealant to the threads. 9. Attach and tighten the cover. Make sure the cover is fully engaged. Required for explosion-proof/flameproof installations only: The cover must be fully engaged to comply with explosion-proof requirements. 11. Re-lock the cover. Rosemount 2130 Level Switch...
  • Page 50 Electrical installation Reference Manual May 2022 00809-0100-4130 12. Connect the power supply. Reference Manual...
  • Page 51: Chapter 5 Operation

    Figure 5-2: Typical Settings for High Level Applications Dry On Wet On Seconds Delay A. Mode “Dry On” and 1 second time delay The "Wet On" mode is recommended for low level alarm installations (Figure 5-3). Rosemount 2130 Level Switch...
  • Page 52: Led Indication Status

    Operation Reference Manual May 2022 00809-0100-4130 Figure 5-3: Typical Settings for Low Level Applications Dry On Wet On Seconds Delay A. Mode “Wet On” and 1 second time delay 5.1.1 Set the mode switch and switching time delay Procedure 1. Select “Dry on” or “Wet on” mode. 2.
  • Page 53: Set The Operating Mode

    LED color Operating modes Description of mode Normal When the LED is red and flashing, it indicates that the Rosemount 2130 may be uncalibrated, successfully calibrated, has an electrical load problem, or has an internal PCB fault. Yellow Self-check When the LED is yellow and flashing, it indicates the same as Normal mode, but also indicates there could be external damage to forks, corroded forks, or internal sensor damage.
  • Page 54 Operation Reference Manual May 2022 00809-0100-4130 Reference Manual...
  • Page 55: Service And Troubleshooting

    In explosion-proof/flameproof and non-incendive installations, do not remove the housing cover when power is applied to the level switch. The housing cover must be fully engaged to meet flameproof/explosion-proof requirements. Rosemount 2130 Level Switch...
  • Page 56: Magnetic Test Point

    A magnetic test point is marked on the side of the housing to allow a functional test of the Rosemount 2130 in the overall system. By touching a magnet to the target, the output from the level switch will change state while the magnet is present.
  • Page 57: Visual Inspection

    A. Output off B. Output on Visual inspection Visually examine the level switch and do not use if it is damaged. Check: • The housing cover, cable glands, and blanking plugs are fitted securely. Figure 6-2: Visual Inspection Rosemount 2130 Level Switch...
  • Page 58: Maintenance

    2. Check the load on direct load switching electronics model. Symptom or indication LED is flashing three times per second. Recommended actions Contact Emerson to report an internal PCB fault is being indicated. Symptom or indication LED is flashing once every two seconds. Recommended actions Contact Emerson to report an uncalibrated device is being indicated.
  • Page 59 Check the electrical installation for a load fault (current is too high or a short-circuit). Symptom or indication Visual inspection found fork damage. Recommended actions Contact Emerson to report the damage and discuss how to get a replacement. Symptom or indication Visual inspection found thick encrustation on the forks. Recommended actions Carefully clean the fork.
  • Page 60: Spare Parts

    Procedure 1. Isolate and disconnect the power to the Rosemount 2130, and insulate the ends of the wires as a safety precaution. There may be more than one power source connected to a relay cassette.
  • Page 61 6. Set the mode switch to “Wet On” with a one second delay, ready for calibration (see Figure 6-5). Figure 6-5: Mode Switch Setting (Replacement Cassette) 7. Reconnect the power supplies to the Rosemount 2130. 6.7.2 Calibrate the replacement cassette Prerequisites Some of the calibration sequence steps are time-dependent and must be carried out within the noted times.
  • Page 62: Opening The Lid (Cover)

    Check the sensor forks are clean and dry. b) Check if anything is jamming or touching the sensor forks. c) Contact Customer Support at Emerson if no fault is found. 11. Set the mode switch to the original setting and wait five seconds.
  • Page 63: Service Support

    00809-0100-4130 May 2022 Service support To expedite the return process outside of the United States, contact the nearest Emerson representative. Within the United States, call the Emerson Instrument and Valve Response Center using the 1-800-654-RSMT (7768) toll-free number. This center, available 24 hours a day, will assist you with any needed information or materials.
  • Page 64 Service and troubleshooting Reference Manual May 2022 00809-0100-4130 Reference Manual...
  • Page 65: Appendix A Specifications And Reference Data

    Emerson is not in a position to evaluate or guarantee the compatibility of the process fluid or other process parameters with the product, options, configuration, or materials of construction selected.
  • Page 66: Performance Specifications

    Specifications and reference data Reference Manual May 2022 00809-0100-4130 A.2.3 Process wetted connections Connections Threaded, Tri Clamp, and flanged process connection options. Materials • 316/316L stainless steel (1.4401/1.4404 dual-certified) • Alloy C (UNS N10002) and Alloy C-276 (UNS N10276) Available for flanged, and selected threaded process connections (¾-in. and 1-in. BSPT (R), and ¾-in.
  • Page 67: Electrical Specifications

    Availability on Cassettes Polarity insensitive Direct Load and Relay electronics Over-current protection Direct Load and PNP/PLC electronics Short-circuit protection Direct Load and PNP/PLC electronics Load-missing protection Direct Load and PNP/PLC electronics Surge protection (to IEC61326) All electronics Rosemount 2130 Level Switch...
  • Page 68: Functional Specifications

    Specifications and reference data Reference Manual May 2022 00809-0100-4130 A.4.2 Terminal connection (wire diameter) Minimum 26 AWG, maximum 14 AWG (0.13 to 2.5 mm ). Note national regulations. A.4.3 Conduit plugs/cable glands Conduit entries for explosion-proof areas are shipped with one Exd plug (loose in bag) and two dust caps fitted.
  • Page 69 Figure A-2: Operating Temperature 176 (80) 176 (80) 149 (65) 2130***E 122 (50) 2130***M 32 (0) 32 (0) -40 (-40) -40 (-40) (80) (260) (80) (180) (-70) (-40) A. Ambient Temperature, °F (°C) B. Process Temperature, °F (°C) Rosemount 2130 Level Switch...
  • Page 70: Dimensional Drawings

    Specifications and reference data Reference Manual May 2022 00809-0100-4130 Dimensional drawings See the Rosemount 2130 web page for all hygienic dimensional drawings. Figure A-3: ¾- and 1-in. Threaded Mounting (Standard Length) 2130***E 2130***M 4.7 (120) 4.7 (120) (182) 13.7 (348)
  • Page 71 F. Ø1.1 (28) for 1-in. thread; Ø0.9 (23) for ¾-in. thread G. 0.5 (13) switchpoint (when mounted vertically) H. 0.5 (13) switchpoint (when mounted horizontally) I. Customer specified fork length (see Table A-2) Dimensions are in inches (millimeters). Rosemount 2130 Level Switch...
  • Page 72 Specifications and reference data Reference Manual May 2022 00809-0100-4130 Figure A-5: Flange Mounting (Standard Length) 2130***E 2130***M 4.7 (120) 4.7 (120) (185) 12.9 (328) (102) (44) (102) (44) A. Allow 1.2 (30) clearance to remove cover B. Aluminum or stainless steel housing C.
  • Page 73 D. Ø1.1 (28) for 1½ -in. or larger flange; Ø0.9 (23) for up to 1-in. flange; Ø0.95 (24) for 1-in. coated flange E. 0.5 (13) switchpoint (when mounted vertically) F. 0.5 (13) switchpoint (when mounted horizontally) G. Customer specified fork length (see Table A-2) Dimensions are in inches (millimeters). Rosemount 2130 Level Switch...
  • Page 74 2022 Emerson. All rights reserved. Emerson Terms and Conditions of Sale are available upon request. The Emerson logo is a trademark and service mark of Emerson Electric Co. Rosemount is a mark of one of the Emerson family of companies. All other marks are the property...