4. Functional description

4.1.

Overview

4.1.1. Input circuit

The input circuit offers the following characteristics :
For all input and output conditions specified in this manual, when the
rectifier is turned on, the ac current will not exceed the maximum steady-
state value.

4.1.2. Output circuit

The output circuit offers the following characteristics :
Emerson Energy Systems
ac rectifying
EMI filtering
inrush current limiting, a walk-in circuit limits the output current
rise to 25 A per second
low and high ac inhibit
power factor compensation
surge voltage protection
ac breaker for input protection
shunt for output dc current sensing
225 A dc circuit breaker for output protection
Rectifier 200I/48 NT5C05C Installation and User Manual