Operation; Standard Settings; Table 15 - Standard Settings For The Rectifier - Emerson 200I/48-NT5C05C Installation And User Manual

Helios modular switch mode rectifier 200i/48
Table of Contents

Advertisement

5. Operation

5.1.

Standard settings

The parameters of the NT5C05CA / CB / CC rectifiers are set as indicated
in Table 15. For different settings refer to User Manual Voltage_level
entitled Voltage Level Limits for Power Plants, Rectifiers and Controllers.

Table 15 - Standard settings for the rectifier

Rectifier float output voltage ( FLOAT )
Rectifier equalize output voltage
( EQUALIZE )
Rectifier high voltage shutdown threshold
Rectifier output current limit
Rectifier start delay
Low ac input disconnect
Low ac input reconnect
High ac input disconnect
High ac input reconnect
Load sharing method
Emerson Energy Systems
Parameter
Rectifier 200I/48 NT5C05C Installation and User Manual
Setting
52.1 ±0.1 V dc
52.8 ±0.1 V dc
56.5 ±0.1 V dc
205 A ±5 A
4 sec
330 ±5 V ac
350 ±5 V ac
475 ±5 V ac
460 ±5 V ac
Slope
45