3.5.
Connecting the dc output terminals to the busbars
The dc outputs of the rectifier are connected to the busbars as illustrated in
Figure 5. There are two methods :
Figure 5 - Connecting the dc to the busbars with a shunt on the battery side or a shunt on
the ground side
+
BAT GRD
+
RECTIFIER
-48V
-
-
+
BAT GRD
+
RECTIFIER
-48V
-
-
SHUNT ON THE GRD SIDE ( PREFERRED CONFIGURATION )
Emerson Energy Systems
BAT GRD ( + ) of the rectifier connected to the CHG/ DISCH
GRD busbar and the –48 V of the rectifier connected to the
CHG BAT busbar
BAT GRD ( + ) of the rectifier connected to the CHG GRD
busbar and the -48V of the rectifier connected to the CHG/
DISCH BAT busbar
CHG / DISCH
GRD BUSBAR
CHG BAT
BUSBAR
SHUNT ON THE BATTERY SIDE
CHG GRD
BUSBAR
CHG / DISCH
BAT BUSBAR
Rectifier 200I/48 NT5C05C Installation and User Manual
LOAD
DISCHARGE
SHUNT
BAT BUSBAR
DISCHARGE
SHUNT
GRD BUSBAR
FUSE
PANEL
Installation 23
FUSE
PANEL
LOAD