34 Functional description

4.2.3. Front panel LEDs

Table 10 - Designation of the LEDs on the front panel

FAN ALM
SEN FAIL
AC ON ( ac voltage monitoring )
The rectifier monitors the input voltage and if the voltage exceeds the set
limit, it will inhibit its operation and trigger a rectifier failure alarm
( RFA ). The rectifier will resume its normal operation automatically when
the specified input voltage has been re-established.
CL ( current limit indicator )
This LED lights up if the rectifier is in current limit. The rectifier limits
the output current to 205 A + 5 A ( adjusted in the factory ), 50% to 105%
of the rated output current.
EQL ( equalize )
Indicates the rectifier is in equalizing mode.
FAN ALM ( fan failure alarm )
This LED lights up when the FAN ALM is activated due to a defect in the
fan system. The fan configuration includes redundancy to ensure the
rectifier will continue working properly if one of the fans fails. If only one
fan fails, a rectifier failure alarm RFA will not be triggered. It is, however,
imperative to repair or change the fan unit as soon as possible to preserve
this redundant feature.
UM5C05C P0745680 Standard 6.00 October 2001
LED
Color
AC ON
Green
CL
Yellow
EQL
Yellow
Red
HVSD
Red
RFA
Red
Red
THSD
Red
Description
Input ac voltage operational
Current Limit
Rectifier is in equalize mode
Fan fail alarm
High voltage shutdown
Rectifier fail alarm
Remote sense fail