Communication and Monitoring

Figure 76 Communication bays and cable location

DB-9
Monitor
Board
(
=
Gland plate
for cable exit
Options—For Assembly Inside the UPS Cabinet
Location
RS-232-1 DB-9 (COM Port 1) - Serial MultiLink Software
(Port Setting 2400 Baud)
RS-232-2 DB-9 (COM Port 2 - Service Access Software
(Port Setting 9600 Baud)
Location
Preferred Device This Location
Top Bay
Relay Card (no port setting req'd)
Mid Bay
Multiport4 (no port setting req'd)
Bottom Bay
OCWeb LB / OC485 (port setting
2400 Baud)
Suggested routing of customer-supplied
communication cables
Notes:
a) All Intellislot cards are supported in any bay.
b) Port sharing is:
- PERMITTED between RS232-x DB9 devices and Relay /
Multiport4 Intellislot cards (i.e., Serial Multilink software
will work from RS232-1 DB9 also when relay card is
inserted in the top bay.
- NOT PERMITTED between RS-232-x D-B9 devices and
OCWeb / OC485 cards (i.e., Serial MultiLink software will
not work from RS232-1 DB-9 when OCWeb card is inserted
in the top bay.
c) Monitor board firmware version will be m131 or greater.
The version may be verified from the UPS LCD (refer to
8.0 - Operator Control Panel and Display).