Table 11
Battery control label description (X102)
BCBB
X-102
Ref Label
1 DRV
2 IN (AUX)
BCB-X3
on U2 Monitor
board
4 USE
3 GND1
5 (1) +12V
X7
on U2 Monitor
6 (3) 0V
board
7 (2) Out
1. Cables connected to X3 BCB must be segregated from power circuits, double insulated and of a typical 0.5 to 1mm2 cross
section area for maximum runs between 25 and 50 meters respectively.
2. Battery temperature sensing cables must be less than 10 m long.
3. 30 and 40kVA UPS models fitted with internal battery and any UPS models fitted with Battery Start kit contain an internal UPS
battery contactor for automatic connection and disconnection of the batteries and the battery circuit breaker undervoltage coil is
not used. Refer to 2.5 - Battery Control for details.
CAUTION
!
Leave terminals open if the corresponding facility is not used. The commissioning engineer
must program the UPS accordingly (e.g., disable battery temperature compensation, enable
internal battery contactor)
2.6.1
Battery Temperature Sensor—Optional
The optional external battery temperature sensor kit, supplied separately from the battery circuit
breaker, contains one probe and one temperature transport board as illustrated in Figure 26. It is
connected to the UPS Monitor Board (either directly or in case of multiple sensors, through the bat-
tery circuit breaker board - see Figures 26 and 27).
Figure 26 Single temperature sensor and monitor board—U2
Monitor Bd
Reference
Label
Description
Battery circuit breaker tripping
DRV
control signal from UPS
Bat CB auxiliary status contact
FB (IN)
(Open contact = CB open)
OL =
Bat CB Board status signal
On Line
(GND = OV from BCB Bd)
GND
GND1
+12V Power supply from
P12
Monitor Bd to Temp Monitoring
Probe & Buffer
GND2
GND2
Buffered Bat temp Probe signal
OUT
from BCB Bd to Monitor Bd
Temperature
Sensor
+
IN
-
TMP-2
Cable W2 is packed with the temperature sensor.
43
Signal status
Normal: H level voltage, BCB can close
Abnormal: L level voltage, BCB trips
Normal: OV when BCB is closed.
Abnormal: open when BCB is open
Normal: 0V, the BCB Board is in use.
Abnormal:. open, the BCB Board is not
in use.
GND1 to GND on U2 board
Power available: 3W.
GND2 to GND on U2 board
Name: W2 L = 30m
NC
12V
OUT
GND
Battery Installation
Monitor
Board
X7
– U2
-12V
BAT-T
GND
UPS