9.0
C
OMMUNICATION
9.1

Communication Interface Port

The Liebert GXT3 UPS has a terminal block on the rear of the UPS unit. Several signals are provided
on this port and are assigned as follows.
9.2

Terminal Block Communication

The terminal block includes eight pins, as shown in Figure 16.

Figure 16 Terminal block communication terminals

9.2.1

Any Mode Shutdown

The purpose of Any Mode Shutdown is to shut down the UPS output by turning Off the rectifier,
inverter and static switch so that there is no power to the loads.
Any Mode Shutdown can be operated locally or remotely:
• Local Any Mode Shutdown can be performed by shorting the pins in Set 3.
• Remote Any Mode Shutdown can be performed using a switch connected to the pins in Set 3 and
mounted at a remote location.
Activation of the Any Mode Shutdown will be logged as an event in the event history log.
NOTE
Remote Power Off will be performed either by NO or NC contact of Any Mode Shutdown.
The current limited source for this optocoupler (+12VDC, 50mA) will be available from UPS.
The connection to UPS for remote connection will be via terminal block connector.
Any Mode Shutdown wiring must conform to all national, regional and local wiring codes and
laws.
WARNING
!
When the Auto-enable output option is selected and the UPS output is disabled using the pins
in Set 3, the Liebert GXT3's output can turn On automatically and without warning if the
connection to the pins in Set 3 is changed.
1
2
Low Battery
On-Battery
Warning
Warning
3
4
Any Mode
Battery Mode
Shutdown
Shutdown