The installation of a multi-module UPS configuration must follow the installation procedure for a sin-
gle UPS module with the additional requirements detailed in this chapter.
In addition to the local EPO push button on the front panel of the UPS module (that stops operation of
that module), the UPS supports also a remote emergency stop to permit simultaneous multi-module
shutdown.
NOTES
1. The remote emergency power off switch must be voltage-free and Normally Open or
Normally Closed.
2. The open voltage supplied is 12VDC, < 20mA
3. This external emergency stop may be supplied with a second set of contacts that can be used
to trip incoming mains or bypass supply circuit breakers supplied by others and fitted with
remote trip units.
4. Normally Closed EPO - X2: 1&2, these terminals are supplied factory-linked on the monitor
board.
Figure 28 Emergency power off connections