1.8.4
Output Dry Contacts
There are three output dry contact relays at the X1 slot (see Figure 4 and Table 6)
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm
(16-20AWG) stranded for maximum runs between 25 and 50m (82-164 ft.) respectively.
Figure 4
Output dry contacts and EPO wiring for firmware before M162
X1
J13
Table 6
Output dry contact relays for firmware before M162
Position
Name
J13.2
BFP_O
J13.3
BFP_S
J13.4
BFP_C
J21.2
INV_O
J21.3
INV_S
J21.4
INV_C
J25.2
ACF_O
J25.3
ACF_S
J25.4
ACF_C
Figure 5
EPO wiring for firmware M200 or later
1.8.5
Emergency Power Off Input
The UPS has an Emergency Power Off (EPO) function that operates by a button on the control panel
or by a remote contact provided by the user. The EPO button is under a hinged, clear plastic shield.
The X2 slot, shown in Figure 4, is the remote EPO input interface. The EPO has an NO/NC contact
point that becomes active when shorting terminals X2: 3 and 4 or open terminal connection X2: 2 and 1
If an external emergency stop facility is required, it is connected terminals X2: 1&2 or X2: 3&4 of the
auxiliary terminal block (X2). It also is connected to the normally open or normally closed remote stop
J21
Description
Bypass feedback protection relay; normally open. Closed when bypass SCR is shorted.
Bypass feedback protection relay center
Bypass feedback protection relay; normally closed. Open when bypass SCR is shorted.
Inverter mode relay; normally open. Closed when UPS is in inverter mode.
Inverter mode relay center
Inverter mode relay; normally closed. Open when UPS is in inverter mode.
Main input fault relay; normally open. Closed when main input is in fault.
Main input fault relay center
Main input fault relay; normally closed. Open when main input is in fault.
J28
EPO-NO
J25
X2
EPO-NC
14
Single Module UPS Installation
2
+12V
X2
J25
EPO-H
EPO-L