Master Programming Level
3.6.12 Program Check
PROGRAMMING
The Program Check feature allows the programmer to view the zones which have been
1=PASSWORD CHANGE
programmed to the Notification Appliance Circuits on the control panel but have not been
2=CLEAR PROGRAM
programmed to Initiating Devices as well as other circuits with no input or output correlations.
3=PROGRAM CHECK
Pressing 3 while viewing Programming Screen #4 will cause the following screen to be displayed:
Programming Screen #4
PROGRAMCHECK
Pressing 1 while viewing the Program Check screen will display an NAC screen similar to the
1=NACS NO INPUT
following.
2=ZONES NO INPUT
3=ZONES NO OUTPUT
Program Check Screen
The example above indicates that NAC 1 has been programmed to Zones 25, 31, 44, 55 and 67 but
no input devices have been programmed to any of these zones. Use the up and down arrow keys to
view all the NAC zones without input assignments for NAC 1, NAC2, NAC 3 and NAC 4.
Pressing 2 while viewing the Program Check screen will display a screen similar to the following:
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
PROGRAM CHECK
1=NACS NO INPUT
2=ZONES NO INPUT
3=ZONES NO OUTPUT
NACS NO INPUT
NAC 1
25 31 44 55 67
ZONES NO INPUT
05 07 09 10 11 1M001
Programming
147