Transferring A Program - Fire-Lite MS-9200UDLS Manual

Addressable fire alarm control panel
Hide thumbs Also See for MS-9200UDLS:
Table of Contents

Advertisement

Transferring a Program

The Remote Download password (default 00000) must be entered to access the Remote Download
feature. Note that the default password can be changed using the Password Change option (refer to
"Password Change" on page 145). Entering the correct password will cause the following screen to
be displayed:
Pressing 1 for Proprietary No (factory default setting), while viewing the Remote Download
screen, will cause the display to toggle from Proprietary No to Proprietary Yes. Each press of the 1
key will cause the display to toggle between Proprietary No and Proprietary Yes. Selecting
Proprietary Yes will program the FACP to allow remote programming downloads from the
PS-Tools programming utility at all times without the need to access the Remote Download screen.
Pressing 2 for Accept Download will cause the following screen to be displayed:
While this screen is displayed, remote programming downloads are allowed regardless of the
Proprietary setting. Exiting this screen will disable any further downloads to the FACP. Also,
following 30 minutes of inactivity (including up/downloading), the Accept Download screen will
time-out, causing the display to return to the System All Normal screen.
6.2 Transferring a Program
The first time that the control panel is downloaded (whether initiated at the jobsite or remotely), a
secret code is loaded in by a Service Terminal. Future upload or download requests cause
verification of the secret code by the control panel before processing of data is allowed. If the
secret code is not verified, the control panel will terminate the request.
While the control panel is communicating with the Service Terminal, one of the DACT's red phone
line active LEDs and the green Kissoff LED will turn on steady.
In order to download the panel (whether initiated at the jobsite or remotely), the following must be
true:
The control panel must be in the Normal Mode of operation. Downloading is not possible if
the panel is in any other mode
There cannot be any active communications ongoing with a Central Station receiver
All active events must be successfully 'kissed-off' by the Central Station(s). The
communicator must be in a standby state with no new information waiting to be transmitted
to a Central Station
MS-9200UDLS/E/C Manual — P/N 52750:F 7/26/2010
REMOTE DOWNLOAD
1=PROPRIETARY
2=ACCEPT DOWNLOAD
*ALLOWING DOWNLOADS*
IF YOU EXIT THIS
SCREEN DOWNLOADS
WILL BE DISABLED!
Remote Site Upload/Download
NO
187

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ms-9200udlseMs-9200udlsc

Table of Contents