by protecting, for example, against power source failures or accidentally tripped circuit breakers.
The server can receive AC input from two different AC power sources.

System AC Power Specifications

Power Cords

Table B-3
lists the various power cables available for use with a HP Integrity rx7620 server. Each
power cord is 15 feet (4.5 meters) in length with a IEC 60320-1 C19 female connector attached to
one end.
Table B-3 Power Cords
Part Number
8120-6895
8120-6897
8121-0070
8120-6903

System Power Specifications

Table B-4
lists the AC power requirements for an HP Integrity rx7620 server. These tables provide
information to help determine the amount of AC power needed for your computer room.
Table B-4 AC Power Specifications
Requirements
Nominal input voltage
Frequency range (minimum -
maximum)
Number of phases
Maximum input current
Maximum inrush current
Power factor correction
Ground leakage current (mA)
Power Required (50 - 60 Hz)
Maximum Theoretical Power
Marked Electrical Power
Typical Maximum Power
110
System Specifications
Description
Stripped end, 240 volt
Male IEC309, 240 volt
Male GB-1002, 240 volts
Male NEMA L6-20, 240 volt
Value
200/208/220/230/240 (VAC rms)
50 - 60 (Hz)
1
12 amps
30 A peak for 15 ms
>0.98
>0.95
<3.0 (ma)
Watts
3156
---
1989
Where Used
International-Other
International-Europe
China
North America/Japan
Comments
Per line cord
Per line cord
At all loads of 50% - 100% of supply rating
At all loads 0f 25% - 50% of supply rating
Per line cord
VA
Comments
3220
See #1 below
2640
12A @ 220 VAC, see note #2
2030
See note #3