Checking The Voltage; Power Source Versus Power Distribution - HP rp7420 Service Manual

Hp 9000 rp7420 server - user service guide, fifth edition
Hide thumbs Also See for rp7420:
Table of Contents

Advertisement

Figure 4-2 Power Source versus Power Distribution
WARNING!
is connected. This voltage is present even when the main power switch is in the OFF position.
To completely remove power, all power cords must be removed from the server. Failure to
observe this warning can result in personal injury or damage to equipment.
NOTE:
System firmware prevents boot when a single power cord configuration is detected.

Checking the Voltage

This section provides voltage check information for use on the customer site. The emphasis
focuses on measuring the voltages at the power cord plug end specified as an IEC 320 C19 type
plug. This end plugs directly into the back of the HP 9000 rp7420 server chassis.
NOTE:
Perform these procedures for each power cord to be plugged directly into the back of
the HP 9000 rp7420 server. If you do not get the expected results from this voltage check, see
"Checking the Voltage (Additional Procedure)" (page
Verifying the Voltage Range of the Receptacle
This measures the voltage between L1 and L2, L1 to ground, and L2 to ground. Three separate
measurements are performed during this procedure. For voltage reference points when performing
the measurements, see
52
Cabling and Powering the Server
Voltage is present at various locations within the server whenever a power source
Figure
4-3.
54).