Release the I/O handle, push the I/O handle down until it ejects the I/O module, and then remove
3.
the I/O module.
CAUTION:
more than one component or blank removed. When removing an active component
permanently, replace it with a blank.
To replace the component, reverse the removal procedure. Be sure the I/O module is fully seated and the
I/O module handle is in the locked position.
Power supply
Before removing the component, be sure to do the following:
•
Verify the status of the power supply to be replaced by reviewing rear panel LEDs and buttons (on
page 56).
•
Be sure that your configuration can support your actions. If the proper redundancy is not in place,
power down the MDS600 before beginning this procedure.
To remove the component:
Disconnect the AC power cord.
1.
For best cooling practices, do not operate the enclosure for extended periods with
Removal and replacement procedures 33