Wide-Ranging Pdu Configurations - HP D7171A - NetServer - LPr Manual

Rack cabling reference
Hide thumbs Also See for D7171A - NetServer - LPr:
Table of Contents

Advertisement

Chapter 3

Wide-Ranging PDU Configurations

Use of four possible 200 - 240 VAC PDU configurations depends upon the power
requirements of the devices in the rack. Table 3-1 shows the characteristics used
to determine how many PDUs are supplied with each rack configuration. In
configurations that use a wide-ranging 10-amp PDU, it will always be plugged
into a wide-ranging 16-amp PDU.
Table 3-2. Number, Type, and Ratings of 208 - 240 VAC PDUs
Wide-
Wide-
Ranging
Ranging
Numbers
16 Amp
10 Amp
(Note 3)
1
0
E7671A (Note 1)
1
1
E7672A (Note 2)
2
0
E7671A + E7671A
2
1
E7671A + E7672A
Note 1 The E7671A includes one 16 amp PDU. The cord which attaches it to the power
source is ordered separately, specifying the cord end required.
Note 2 The E7672A includes one 16 amp PDU, one 10 amp PDU, and the cord which
attaches them together. The cord which attaches the 16 amp PDU to the power source is
ordered separately, specifying the cord end required.
Note 3 The 10-amp PDU can be ordered as an accessory using part number E7670A.
Your wide-ranging PDU configuration is determined using Table 3-2 and by
application of the following guidelines:
1. One 16-amp PDU is supplied for each Uninterruptible Power Supply
(UPS) in a rack.
2. The total number of each kind of receptacle is figured for equipment to
be mounted in each rack.
Part
C19
Receptacles
2
2
4
4
Cabling Reference Information
C13
Total Amps
Receptacles
6
16
15
16
12
32
21
32
47

Advertisement

Table of Contents
loading

Table of Contents