Install the HP Model 30/FC High Availability Disk Array

1. Check Power Requirements
Refer to the disk array DC power requirements in the Reference chapter of the Hewlett-Packard Model 30/FC High
Availability Disk Array Service Manual (part number A3661-90002) to make sure the installation site meets these
requirements.
The HP Model 30/FC High Availability Disk Array uses 200VAC to 240VAC nominal; 110VAC is not supported. One
power distribution unit (PDU) in the cabinet can provide sufficient power for one, two, or three disk arrays. The disk
array and HP FC-AL hub are connected to the PDU; the PDU is connected to an UPS.
Make sure the UPS is capable of supplying an amount of power equal to the sum of the VA units required to power all
the systems and peripherals installed in the cabinet.
Consider the type of PDU that is required. PDUs have power inlets and outlets that impinge on clearances necessary to
fully open the disk array's fan pack door. Table 1 specifies the required PDUs for various hardware configurations
installed in one cabinet.
Table 1 – PDU Requirements
PDU part
PDU product
number
number
E5929-63001
E5929A
E5931A
E5932A
E4456-63001
E4456B
E4457-63001
E4457B
C2786-63006
E4456A
C2786-63007
E4457A
Description
- Universal PDU
- Ten C-13 and one C-19
outlets
- One C-20 inlet for
detachable cords
- N. America 220 V PDU
- Ten C-13 outlets
- Attached 3 m power
cord with L6-30P plug
- Europe 220 PDU
- Ten C-13 outlets
- Attached 3 m power
cord without plug
- N. America 220 V PDU
- Ten C-13 and one C-19
outlets
- Attached power cord
with L6-20P plug
- Europe 220 V PDU
- Ten C-13 and one C-19
outlets
- Attached power cord
without a plug
- N. America
220 V PDU
- Ten C-13 outlets
- Attached power cord
with L6-20P plug
- Europe 220 V PDU
- Ten C-13 outlets
- Attached power cord
without plug
Typical application
Racking restrictions
C-19 outlet is for SPUs
Must be racked on rails at or
requiring a 20-amp
above 4 EIAs to clear the
connector.
C-19 outlet.
C-20 inlet facilitates a
If the C-19 outlet is not
universal set of
used, must be racked on
detachable power cords.
rails at or above 1 EIA to
Typically, for external
clear the C-20 inlet.
UPS applications
Attached to a 3.0 or 5.5
None
kva N. American UPS
Attached to a 3.0 or 5.5
None
kva European UPS
C-19 outlet is for SPUs
Must be racked on rails at or
requiring a 20-amp
above 4 EIAs to clear the
connector.
C-19 outlet.
Power cord typical for
If the C-19 outlet is not
N. America wall outlet
used, must be racked on the
connection.
bottom of the rack without
rails.
C-19 outlet is for SPUs
Must be racked on rails at or
requiring a 20-amp
above 4 EIAs to clear the
connector.
C-19 outlet.
Power cord has stripped
If the C-19 outlet is not
ends for attaching
used, can be racked on the
localized plug.
bottom of the rack without
rails.
None
Power cord has stripped
None
ends for attaching
localized plug.
14