Rack Tie-Down Option Kit - HP BL685c - ProLiant - 4 GB RAM Site Planning Manual

Hp bladesystem c-class site planning guide
Hide thumbs Also See for BL685c - ProLiant - 4 GB RAM:
Table of Contents

Advertisement

Rear door: The clearance between the rear of the enclosure and the rear rack door must be a
minimum of 175 mm (6.9 in) to accommodate system cabling.
Side: The clearance between the installed rack component and the side panels of the rack must be a
minimum of 70 mm (2.75 in).
Width: 483 mm (19 in)
Depth: Maximum clearance between front and rear RETMA rails is 864 mm (34 in). Minimum
clearance for round-hole racks is 627 mm (24.7 in). Minimum clearance for square-hole racks is
635 mm (25 in).
The rack must be able to accept the adjustable rack rails that are shipped with each enclosure:
Minimum rail length: 635 mm (25 in)
o
Maximum rail length: 864 mm (34 in)
o

Rack tie-down option kit

The HP 10000 G2 Series Rack Tie-Down Option Kit enables you to secure HP 10000 G2 Series Racks to
the floor.
The following table indicates where the holes are to be drilled to secure the rack to the floor. The
distances are measured from the holes on the tie-downs. To drill your holes, contact your building
structural engineer. After your holes have been drilled, insert a bolt with a washer into each hole,
securing the rack to the floor.
Callout
A
B
C
D
E
For more information, see the HP 10000 G2 Series Rack Tie-Down Option Kit Installation Instructions.
600W distance
470 mm (18.0 in)
235 mm (9.3 in)
987.1 mm (38.9 in)
231 mm (9.1 in)
462 mm (18.2 in)
Environmental requirements 28