HP BladeSystem enclosure environmental specifications

Specification
Temperature range*
Operating
Non-operating
Wet bulb temperature
Operating
Non-operating
Relative humidity
(noncondensing)**
Operating
Non-operating
* All temperature ratings shown are for sea level. An altitude derating of 1°C per 304.8 m (1.8°F per 1000 ft) to
3048 m (10,000 ft) is applicable. No direct sunlight allowed. Upper operating limit is 3,048 m (10,000 ft) or 70
kPa/10.1 psia. Upper non-operating limit is 9,144 m (30,000 ft) or 30.3 kPa (4.4 psia).
** Storage maximum humidity of 95% is based on a maximum temperature of 45°C (113°F). Altitude maximum for
storage corresponds to a pressure minimum of 70 kPa (10.1 psia).

Rack and accessory footprints

When accessories such as extensions and stabilizing kits are added to a particular rack, the footprint of
the rack extends into the rack rear row and infringes upon necessary clearances.
Footprint for a 600 mm rack configuration with an extension kit installed (598 mm wide x 1184.9 mm
deep):
Value
10°C to 35°C (50°F to 95°F)
-30°C to 60°C (-22°F to 140°F)
28ºC (82.4ºF)
38.7ºC (101.7ºF)
20% to 80%
5% to 95%