Recommended operating environment

To help ensure continued safe and reliable equipment operation, install or position the rack in a well
ventilated, climate-controlled environment.
Air inlet temperature to the rack should be between 20 to 25ºC under normal operating conditions in the
data center, per ASHRAE standard TG9 HDEC.
The following table shows product technical requirements based on customer environments.
Environment
Controlled
computer room
Controlled office 2
Uncontrolled
office
Home
Light industrial
Portable/mobile 4
Special
The maximum elevation for all operating environmental classes is 3050 m.
1
2
Dry bulb temperature is the regular ambient temperature. Derate maximum dry bulb temperature 1ºC/300 m above
900 m.
3
The values in each row meet or exceed the stated industry equivalent class specifications.
4
With installed media, the minimum temperature is 10ºC and maximum relative humidity is limited to 80%. Specific
media requirements may vary.
5
Allowable: equipment design extremes as measured at the equipment inlet.
Recommended: target facility design and operational range.
6
7
Must be noncondensing environment.
8
Local product groups must make business decisions for the appropriate values.
The operating temperature inside the rack is always higher than the room temperature and is dependent
on the configuration of equipment in the rack. Check the TMRA for each piece of equipment before
installation.
CAUTION:
Do not permit optional equipment to impede airflow around the enclosure or to increase the
internal rack temperature beyond the maximum allowable limits.
Do not exceed the manufacturer's TMRA.
Operating Environment (ambient)
Temperature (ºC, dry bulb)
Industry
Allowable
4
Recommended
equivalent
3
,5
ASHRAE
1
15 to 32
20 to 25
10 to 35
20 to 25
3
5 to 35
NA
3
5 to 35
NA
4
5 to 40
NA
5 to 40
NA
Product specifications are controlled by contract or other requirements.
To reduce the risk of damage to the equipment when installing third-party options:
1
2
Relative humidity %;
noncondensing
6
Allowable
5
Recommended
20 to 80
40 to 55
20 to 80
40 to 55
8
8 to 85
NA
8
8 to 85
NA
8
8 to 90
NA
8
8 to 90
NA
6
Dew
Rate of
point
chg
(max)
7
(ºC/hr,
max)
17
5
21
5
8
28
NA
8
8
28
NA
8
8
28
NA
8
8
28
NA
8
Environmental requirements 18