Hayward Pro Logic Operation Manual page 22

Automation and chlorination
Hide thumbs Also See for Pro Logic:
Table of Contents

Advertisement

Filter Operation
If "Spa Spillover" is selected, the Pro Logic will automatically switch the pool/spa suction and return
valves to "spillover" at the start of the programmed pool filtering time period or when the super-
chlorinate function is turned on. The valves will remain in this position for the remainder of the super-
chlorinate period. This option is usually preferable because both the pool and spa water will be
filtered and sanitized.
If "Pool Only" is selected, then the Pro Logic will switch the pool/spa valves to the "pool only"
position at the start of the programmed pool filtering time period or when the super-chlorinate func-
tion is turned on. This may be desirable on some systems with in-floor cleaners because it allows the
cleaner to operate all the time the pool is being filtered and/or the super chlorinate is running.
V1=Aux1, V2=Aux2
This menu appears only if the Pool/Spa Setup is "Pool Only" or "Spa Only". When enabled, Valve 1
(return) will follow the Aux1 output and Valve 2 (suction) will follow the Aux2 output. When disabled
(default), the return and suction pool/spa valves function normally.
Filter Off Valve Change
This menu appears only if Pool/Spa setup is set to "Pool and Spa". When enabled (default), the filter
pump will shut off for 35 seconds whenever the Pool/Spa valves are turning. The pump will NOT shut
off when the heater has Cooldown enabled and is either on or in the Heater Cooldown mode.
Filter Config.
Push to access pump options
+ to view/change
Move to previous/next configuration menu
Filter Name
Rotates between all available names
Pool Filter
Move to next menu item
Filter Pump
Rotates between 1-speed (default), 2-speed and variable speed options
1 Speed
Move to next menu item
if "Variable Speed" is selected
Lowest Speed
Adjust the lowest speed desired for variable speed operation
10%
Move to next menu item
if "Variable Speed" is selected
Highest Speed
Adjust the highest speed desired for variable speed operation
100%
Move to next menu item
Flow Monitor
Toggle between Enabled and Disabled
Disabled
Move to next menu item
Freeze Protect
Toggle between Enabled (default) and Disabled Freeze Protection
Enabled
Move to next menu item or previous/next configuration menu
if "Freeze Protect" is enabled
and "2-speed Filter" is selected
Freeze Protect
Toggle between high speed (default) and low speed
High Speed
Move to next menu item
if "Freeze Protect" is enabled
and "Variable Speed" is selected
Select the desired Freeze Protection speed from Filter Lowest to Filter Highest speed
Move to next menu item
if "Freeze Protect" is enabled
Freeze Temp
Adjust the desired freeze protection temperature (33ºF - 42ºF)
38ºF
Move to next menu item
External Input
Toggle between Enabled and Disabled (default)
Disabled
Move to previous/next configuration menu
Filter Name
The Pro Logic allows you to assign any one of a number of names (e.g. "Filter Pump, Pool Filter, Spa
Filter, etc.) to the filter relay. This will make the Pro Logic more user friendly to the homeowner when
they want to control the filter equipment. A sheet of small name labels is included with the Pro Logic
main unit and each remote display/keypad so that appropriate pushbuttons can be labeled the same
as the name that you have assigned.
(default)
Flow Monitor
19
Aux1 Group
The Aux1 Group function allows the user to perform multiple tasks with a single push of the "Aux1"
button. When setting up a Group function, refer to page 15 for specific programming information.
There are two Group menus; the first menu determines how the group command will be initiated
(Manual On/Off, Countdown Timer, or Timeclock) and the second menu selects the desired functions
and their respective control parameters.
When activating Group functions, be aware that the most recent Group function that is initiated will
override any previous Group function.
Aux1 External Input Interlock
When Aux1 External Input Interlock is enabled, the Aux1 output will be forced off when the external
input is active. This will have precedence over freeze protection. Aux1 External Input Interlock is not
available for solar, low speed filter pump, dimmer, group, super chlorinate, or pH dispense functions.
Aux1 Freeze Protection
This function protects the pool, plumbing, and equipment against freeze damage. If Freeze Protection
is enabled and the AIR temperature sensor falls below the selected freeze protection temperature, the
Pro Logic will turn on the aux relay to circulate the water. IMPORTANT: this only enables operation
of the AUX output during freeze--see the "Filter Pump Config." menu to enable freeze protection for
the main circulation system. Freeze Protection is not available for low speed filter pump, dimmer,
group, super chlorinate or pH dispense functions.
Aux1 Pump Speed
This is the speed of the filter pump when the Aux1 output is on. The default selection is "Settings
Menu". This is the speed of the pump that has been selected in the Settings Menu for normal filter
operation. If an alternate speed is desired when the Aux1 output is on, push "+" or "-" and select from
"Lowest" to "Highest" in 5% increments.
PL-PS-8-V models only:
Aux3 - Aux7 only
PL-PS-16-V models only: Aux7 - Aux14 only
Aux7 Config.
Push to access Virtual Aux options
+ to view/change
Move to previous/next configuration menu
Aux7 Name
Rotates between all available names
Cleaner
Move to next menu item
Aux7 Relay
Toggle between Standard (default) and ColorLogic (must be detected)
Standard
Move to next menu item or previous/next configuration menu
Aux7 Function
Rotates between Super Chlorinate,
Group
Move to next menu item
Aux7 Group
Rotates between Manual On/Off (default),Countdown Timer and Timeclock
Timer: None(Manual)
Move to next configuration menu item
Aux7 Group
Options available depend on the function that is selected
Filter: Unaffected
Move to previous/next menu item or next configuration menu
For more information on the Group function, refer to page 15. If neither Super Chlorinate, ColorLogic or a Group
can be assigned to a Virtual Aux button, the following will be displayed:
No Virtual
Functions Available
Group and Manual On/Off
28