UDM 35/40 PANEL METER USER MANUAL
Navigating & Programming within the Linearization Menu
As
appears, press
ignore or enable linearization
and advance to next step. If you chose YES, you will be prompted to
enter the number of Linearization Points,
button
to select the position, and the up
the numerical value, from 01-16. Press enter
Next, the correlation between the inputs and outputs must be defined in
the program.
"In.01" will be displayed. Press
use the
and
advance. "Ou.01" will display next. Again, using the escape key
toggle to the appropriate position. Use the
value. Press enter
each set of Inputs and Outputs, up through a maximum of 16. Press the
enter key
to confirm. Press
sequence.
Alarm Set-point Programming
Up to 4 alarm set-points may be configured. You may configure each set
point using the following parameters, in order, as shown below:
Minimum set-point limit
Maximum set-point limit
Set-point setting
followed by
. Press
to toggle through the positions, and
keys to select the value. Press
to confirm and advance. Repeat this procedure for
to advance to the next program step
and
keys to choose to
to confirm your choice
using the escape
/down
buttons to select
to confirm and advance.
to confirm and
and
keys to select the
,
11