Direct starting electronic control panel for pressure booster with display and general disconnecting switch with door lock (32 pages)
Summary of Contents for SALUPO MULTIPLUS 1
Page 1
ITA/ENG ITA/ENG rev.5 31/08/2021 rev.6 11/01/2023 MULTIPLUS 1 MULTIPLUS 1 SA684.xx / SA687.xx SA684.xx / SA687.xx MANUALE DI ISTRUZIONE E INSTALLAZIONE MANUALE DI ISTRUZIONE E INSTALLAZIONE INSTRUCTION AND INSTALLATION MANUAL INSTRUCTION AND INSTALLATION MANUAL Quadro elettronico avviamento diretto 1 motore per acque pulite e reflue con display e sezionatore blocca porta.
1. ISTRUZIONI GENERALI PER L’INSTALLAZIONE ITALIANO Assicurarsi che la linea sia protetta, secondo le normative, in funzione dell'applicazione. Accertarsi che la potenza e la corrente di targa del motore rispecchino i limiti di impiego del quadro. Installare il quadro in ambienti adatti al suo grado di protezione IP65. Per il fissaggio dell'involucro, utilizzare le staffe per i box 03-04 e le apposite predisposizioni per i restanti box.
3. ESEMPI APPLICATIVI Di seguito vengono illustrati alcuni esempi pratici delle applicazioni che è possibile realizzare con il quadro MULTIPLUS 1. φ MARCIA A SECCO CON COS 1 INGRESSO 2 INGRESSI START/ STOP ACQUE PULITE 1 INGRESSO 1 INGRESSO 2 INGRESSI...
Page 5
3. ESEMPI APPLICATIVI ITALIANO Di seguito vengono illustrati alcuni esempi pratici delle applicazioni che è possibile realizzare con il quadro MULTIPLUS 1. ACQUE REFLUE ACQUE BIANCHE ACQUE NERE ALARM START ALARM STOP START STOP 4-20mA bar 4-20mA metri TRANSD. 4-20m A ALARM PIEZOR.
4. SCHEMI DI COLLEGAMENTO 4.1 Schema di collegamento SA684.xx SCHEDA ESPANSIONE CONDENSATORE 3 4 5 6 7 8 9 10 12 13 14 15 16 G.MIN G.MAX1 G.MAX2 G.ALAR AVV. ANALOG PR.STA PR.EME MOTOR 1 ALARM 4-20mA MOTORE CONDENSATORE A BORDO POMPA AVV.
ITALIANO 4. SCHEMI DI COLLEGAMENTO 4.2 Schema di collegamento SA687.xx SCHEDA ESPANSIONE 3 4 5 6 7 8 9 10 12 13 14 15 16 G.MIN G.MAX1 G.MAX2 G.ALAR ANALOG PR.STA PR.EME MOT1 SUPPLY 4-20mA ALARM LINEA DI ALIMENTAZIONE 400 Vac 50/60 Hz LEGENDA MOTORE SONDE DI LIVELLO O GALLEGGIANTE MINIMO...
5. PROGRAMMAZIONE APPLICAZIONE 5.1 Programmazione rapida 4-20mA metri APPLICAZIONE 4-20mA bar APPLICAZIONE LANGUE FRANCAISE V3.0 ACQUE REFLUE ACCENSIONE QUADRO APPLICAZIONE LANGUAGE ENGLISH V3.0 ACQUE PULITE LINGUA APPLICAZIONE ITALIANO V3.0 COSFI LINGUA APPLICAZIONE SETUP PREMI ITALIANO V3.0 COSFI PAGE + MAN 10s PREMUTO SI VISUALIZZA LA RESTANTE PARTE DEI PARAMETRI LA CENTRALINA HA IMPOSTABILI IN FUNZIONE ALL’APPLICAZIONE SCELTA:...
5. PROGRAMMAZIONE ITALIANO 5.2 Applicazione cosφ SERVE AD IMPOSTARE UN TEMPO DI ATTESA RIEMPIMENTO CHE SI AVVII OGNI VOLTA CHE LA CENTRALINA RILEVA UNA CONDIZIONE DI MARCIA A SECCO RANGE 1min ÷ 99h 59min ATTESA RIEMPIM. 0 h 30 m SERVE A IMPOSTARE MANUALMENTE VALORE DEL COS φ...
5. PROGRAMMAZIONE 5.3 Applicazione acque pulite NELLA MODALITÀ 2 INGRESSI IL COMANDO ESTERNO È: OFF G.MIN E G.MAX CHIUSI (DISABILITA MOTORE) ON G.MIN E G.MAX APERTI (ABILITA MOTORE) COMANDO ESTERNO 2 INGRESSI SERVE AD IMPOSTARE MANUALMENTE IL VALORE NELLA MODALITÀ 1 INGRESSO DELLA SENSIBILITÀ...
ITALIANO 5. PROGRAMMAZIONE 5.5 Applicazione 4-20mA bar SERVE AD IMPOSTARE IL FONDO SERVE AD IMPOSTARE IL RITARDO SCALA DEL TRASDUTTORE PER L’AVVIO DEL MOTORE QUANDO UTILIZZATO LA PRESSIONE DELL’IMPIANTO SCENDE AL DI SOTTO DELLA TRASDUTTORE PRESSIONE START 25 bar SERVE AD IMPOSTARE LA RANGE 1min ÷...
5. PROGRAMMAZIONE 5.6 Applicazione 4-20mA metri SERVE AD IMPOSTARE IL LIVELLO SERVE AD IMPOSTARE IL LIVELLO SERVE AD IMPOSTARE IL FONDO DI ACQUA SOTTO IL QUALE LA DI ACQUA SOPRA IL QUALE LA SCALA DELLA SONDA UTILIZZATA CENTRALINA SPEGNE IL MOTORE CENTRALINA AVVIA IL MOTORE RANGE 1.0 ÷...
5. PROGRAMMAZIONE ITALIANO 5.7 Programmazione avanzata OFF. ESCLUDE IL CONTROLLO SULLA CORRENTE MINIMA CORRENTE MINIMA SERVE AD IMPOSTARE IL TEMPO DI RIARMO SULLA CORRENTE MINIMA SERVE AD IMPOSTARE LA SERVE AD IMPOSTARE LA CORRENTE MASSIMA DI CORRENTE MINIMA N.B.: NELL’APPLICAZIONE SOVRACCARICO DEL MOTORE DEL MOTORE φ...
Page 14
5. PROGRAMMAZIONE STABILE AVVIA IL MOTORE CON UN SERVE AD IMPOSTARE IL IMPULSO SUL PULSANTE MAN; RITARDO SULL’ATTIVAZIONE ARRESTA IL MOTORE CON UN SERVE AD IMPOSTARE DELL’USCITA DI ALLARME IMPULSO SUL PULSANTE RESET L’ATTESA PRESENZA RETE RANGE 1 ÷ 250min RANGE 1 ÷...
6. FUNZIONAMENTO GENERALE DEL QUADRO ITALIANO 6.1 Funzionamento generale ACCENSIONE QUADRO SETUP PREMI QUESTA SCHERMATA VIENE VISUALIZZATA SOLO SE LA FUNZIONE ATTESA RETE È ABILITATA PAGE + MAN 10s NEL MENÙ SETUP. PER ESCLUDERE IL TEMPO DI ATTESA PREMERE RESET ATTESA RETE 1 m RESET PER AVVIO A SEGUIRE SI VISUALIZZANO LE SCHERMATE DI FUNZIONAMENTO...
6. FUNZIONAMENTO GENERALE DEL QUADRO 6.3 Applicazione acque pulite SERVE AD AVVIARE MANUALMENTE IL MOTORE 400 V 13.2 A SOLO IN MODALITÀ PULSANTE MANUALE STABILE OFF: DISABILITA MOTORE MOTORE STOP ON: ABILITA MOTORE 0.0 A LA SEGUENTE SCHERMATA VISUALIZZA: - TENSIONE MISURATA COMANDO ESTERNO - CORRENTE ASSORBITA - ORE DI FUNZIONAMENTO DEL MOTORE...
ITALIANO 6. FUNZIONAMENTO GENERALE DEL QUADRO 6.5 Applicazione 4-20mA bar SERVE AD AVVIARE MANUALMENTE IL MOTORE 400 V 13.2 A 10.5 bar SOLO IN MODALITÀ PULSANTE MANUALE STABILE MOTORE STOP LA SEGUENTE SCHERMATA VISUALIZZA: 0.0 A - TENSIONE MISURATA - CORRENTE ASSORBITA - PRESSIONE IMPIANTO VISUALIZZA LA PRESSIONE - ORE DI FUNZIONAMENTO DEL MOTORE...
7. MANUTENZIONE MOTORE 7.1 Programmazione manutenzione motore SERVE AD IMPOSTARE LA MANUTENZIONE MOTORE RANGE 1÷ 99999h ACCENSIONE MANUTENZIONE MOT QUADRO IMPOSTATA 500h MANUTENZIONE MOT IMPOSTATA OFF ESCLUDE LA MANUTENZIONE MOTORE MANUTENZIONE MOT SETUP PREMI IMPOSTATA PAGE + MAN 10s QUESTA SCHERMATA VISUALIZZA L’AZZERAMENTO DEL TEMPO DI MANUTENZIONE ULTIMA MANUTENZ.
8. DATA LOGGER ITALIANO 8.1 Data logger allarmi Il data logger allarmi serve a visualizzare in ordine decrescente gli ultimi 20 allarmi salvati. La centralina insieme all’allarme registra anche le ore di funzionamento del motore in cui è stato generato. ACCENSIONE QUADRO AL.
9. RICERCA GUASTI E SOLUZIONI PROPOSTE PROBLEMI COMUNI POSSIBILI CAUSE SOLUZIONI Alimentare il quadro rispettando Alimentazione di rete Off la tensione di ingresso Il display non si accende Manopola del sezionatore su 0 Posizionare la manopola del sezionatore su 1 Collegare correttamente il cavetto flat Cavetto flat all’interno del quadro scollegato dalla scheda madre al display...
ITALIANO 10. MESSAGGI DI ALLARME DATA SCHERMATA DESCRIZIONE LOGGER Se la corrente assorbita dal motore supera quella impostata nel setup, la CORRENTE MASSIMA centralina spegne il motore ed il display visualizza il seguente messaggio. PREMI RESET Se la corrente assorbita dal motore risulta inferiore a quella impostata nel CORRENTE MINIMA setup, la centralina spegne il motore ed il display visualizza il seguente PREMI RESET...
Page 22
INDEX 1. General instructions for installing 2. Warnings 3. Application examples 4. Wiring diagrams 4.1 Wiring diagrams SA684.xx 4.2 Wiring diagrams SA687.xx 5. Programming 5.1 Fast programming 5.2 Application cosφ 5.3 Application clean water 5.4 Application sewage 5.5 Application 4-20mA bar 5.6 Application 4-20mA meters 5.7 Advanced programming 6.
Page 23
1. GENERAL INSTRUCTIONS FOR INSTALLING ENGLISH Make sure power supply is protected up to standard depending on application. The power of the motor has to be within the control panel's limits of use. Install the control panel in an environment appropriate to its IP65 degree of protection. To fix the enclosure, use the brackets for the boxes 03-04 and the special predispositions for the remaining boxes.
3. APPLICATION EXAMPLES Below are some practical examples of applications that can be implemented with the MULTIPLUS 1 control panel. DRY RUNNING COSφ 1 INPUT 2 INPUTS START/ STOP CLEAN WATER 1 INPUT 1 INPUT 2 INPUTS START/ STOP ALARM...
Page 25
3. APPLICATION EXAMPLES ENGLISH Below are some practical examples of applications that can be implemented with the MULTIPLUS 1 control panel. SEWAGE WHITE WATERS BLACK LIQUOR ALARM START ALARM STOP START STOP 4-20mA bar 4-20mA meters TRANSD. 4-20m A ALARM PIEZOR.
4. WIRING DIAGRAMS 4.1 Wiring diagram SA684.xx EXPANSION BOARD CAPACITOR 3 4 5 6 7 8 9 10 12 13 14 15 16 G.MIN G.MAX1 G.MAX2 G.ALAR AVV. ANALOG PR.STA PR.EME MOTOR 1 4-20mA ALARM MOTOR CAPACITOR INSIDE PUMP AVV. MOTOR POWER SUPPLY 230 Vac 50/60 Hz...
Page 27
ENGLISH 4. WIRING DIAGRAMS 4.2 Wiring diagram SA687.xx EXPANSION BOARD 3 4 5 6 7 8 9 10 12 13 14 15 16 G.MIN G.MAX1 G.MAX2 G.ALAR ANALOG PR.STA PR.EME MOT1 SUPPLY 4-20mA ALARM POWER SUPPLY 400 Vac 50/60 Hz MOTOR LEVEL PROBES OR MINIMUM FLOAT SWITCH LEVEL PROBES OR MAX1 FLOAT SWITCH...
Page 28
5. PROGRAMMING APPLICATION 5.1 Fast programming 4-20mA metri APPLICATION 4-20mA bar APPLICATION LANGUE FRANCAISE V3.0 SEWAGE IGNITION CONTROL PANEL APPLICATION LANGUAGE ENGLISH V3.0 CLEAN WATER LINGUA APPLICATION ITALIANO V3.0 COSFI LANGUAGE APPLICATION SETUP PRESS ENGLISH V3.0 COSFI PAG + MAN 10s PRESSING IT YOU WILL SEE THE REMAINING PART OF THE PARAMETERS THE MOTHERBOARD HAS THAT CAN BE SET ACCORDING TO THE APPLICATION CHOSEN:...
Page 29
5. PROGRAMMING ENGLISH 5.2 Application cosφ IT IS USED TO SET A FILLING WAITING TIME WHICH INTERVENES EVERY TIME THE MOTHERBOARD DETECTS A DRY RUNNING CONDITION RANGE 1min ÷ 99h 59min WAITING FILLING 0 h 30 min IT IS USED TO SET MANUALLY THE COSφ...
Page 30
5. PROGRAMMING 5.3 Application clean water IN 2 INPUTS MODE THE EXTERNAL COMMAND IS: OFF G.MIN AND G.MAX CLOSED (DISABLE MOTOR) ON G.MIN AND G.MAX OPEN (ENABLE MOTOR) EXTERNAL COMMAND 2 INPUTS IT IS USED TO SET IN 1 INPUT MODE THE MANUALLY THE PROBES EXTERNAL COMMAND IS: SENSITIVITY VALUE...
Page 31
5. PROGRAMMING ENGLISH 5.5 Application 4-20mA bar IT IS USED TO SET THE FULL IT IS USED TO SET THE DELAY SCALE OF THE TRANSDUCER FOR STARTING THE MOTOR WHEN USED THE SYSTEM PRESSURE DROPS BELOW THE TRANSDUCER START PRESSURE 25 bar IT IS USED TO SET THE RANGE 1min ÷...
5. PROGRAMMING 5.6 Application 4-20mA meters IT IS USED TO SET THE WATER LEVEL IT IS USED TO SET THE WATER LEVEL IT IS USED TO SET THE FULL BELOW WHICH THE MOTHERBOARD ABOVE WHICH THE MOTHERBOARD SCALE OF THE PROBE USED TURNS OFF THE MOTOR STARTS THE MOTOR RANGE 1.0 ÷...
Page 33
5. PROGRAMMING ENGLISH 5.7 Advanced programming OFF EXCLUDES THE CONTROL ON THE MINIMUM CURRENT MINIMUM CURRENT IT IS USED TO SET THE RESET TIME ON THE MINIMUM CURRENT IT IS USED TO SET THE IT IS USED TO SET THE OVERLOAD MAXIMUM CURRENT MINIMUM CURRENT N.B.: ABSENT ON...
Page 34
5. PROGRAMMING STABLE STARTS THE MOTOR WITH IT IS USED TO SET THE A PULSE ON THE MAN BUTTON; DELAY ON THE ACTIVATION STOPS THE MOTOR WITH A PULSE IT IS USED TO SET THE OF THE ALARM OUTPUT ON THE RESET BUTTON MAINS SUPPLY WAITING RANGE 1 ÷...
Page 35
6. GENERAL FUNCTIONING OF THE CONTROL PANEL ENGLISH 6.1 General functioning IGNITION CONTROL PANEL SETUP PRESS THIS SCREEN IS DISPLAYED ONLY IF THE MAINS SUPPLY WAITING FUNCTION IS ENABLED PAG + MAN 10s IN THE SETUP MENU. TO EXCLUDE THE WAITING TIME PRESS RESET MAINS WAIT.
Page 36
6. GENERAL FUNCTIONING OF THE CONTROL PANEL 6.3 Application clean water IT IS USED TO START THE MOTOR MANUALLY 400 V 13.2 A ONLY IN STABLE MANUAL BUTTON MODE OFF: DISABLE MOTOR STOP MOTOR ON: ENABLE MOTOR 0.0 A THE FOLLOWING SCREEN DISPLAYS: - MEASURED VOLTAGE EXTERNAL COMMAND - ABSORBED CURRENT...
6. GENERAL FUNCTIONING OF THE CONTROL PANEL ENGLISH 6.5 Application 4-20mA bar IT IS USED TO START THE MOTOR MANUALLY 400 V 13.2 A 4.5 bar ONLY IN STABLE MANUAL BUTTON MODE STOP MOTOR THE FOLLOWING SCREEN DISPLAYS: 0.0 A - MEASURED VOLTAGE - ABSORBED CURRENT - SYSTEM PRESSURE...
7. MOTOR MAINTENANCE 7.1 Motor maintenance programming IT IS USED TO SET THE MOTOR MAINTENANCE RANGE 1÷ 99999h IGNITION MOT. MAINTENANCE CONTROL PANEL 500h MOT. MAINTENANCE OFF EXCLUDES THE MOTOR MAINTENANCE MOT. MAINTENANCE SETUP PRESS PAGE + MAN 10s THIS SCREEN DISPLAYS THE MAINTENANCE TIME RESET LAST MOTOR MAINTENAN.
Page 39
8. DATA LOGGER ENGLISH 8.1 Alarm data logger The alarm data logger is used to display the last 20 stored alarms in descending order. The motherboard together with the alarm also records the motor operating hours in which it was generated.
Page 40
9. TROUBLESHOOTING AND PROPOSED SOLUTIONS FREQUENT PROBLEMS CAUSES OPERATION Feed the control panel respecting o supply the input voltage Display off Switch set on 0 Set the switch on 1 Connect the flat cable from the motherboard The flat cable inside the control panel to the display is not connected Set manually the maximum current the 25%...
ENGLISH 10. ALARM MESSAGES DATA SCREEN DESCRIPTION LOGGER MAXIMUM CURRENT If the current absorbed by the motor exceeds that adjusted in the setup, the motherboard will turn off the motor and the display will show the following PREMI RESET message. If the current absorbed by the motor is lower than the current set in the setup, MINIMUM CURRENT the motherboard will turn off the motor and the display will show the following...
12. DICHIARAZIONE DI CONFORMITA’ CE E UK DECLARATION OF CONFORMITY CE AND UK Manufacturer Fabbricante / SALUPO S. r.l. C/da Pietra di Roma – Via Vicolo VI, n°2 98070 Torrenova (ME) ITALY Dichiara sotto la propria responsabilità che i prodotti:...
Dear customer, Salupo S.r.l. would like to thank you for your preference. The product you have purchased is covered by the warranty as shown below. We guarantee the quality and smooth operation of our products up to 24 months, starting from the date of purchase, against manufacturing defects and except for the following items for which we guarantee up to 12 months: SQ702.xx;...