From Fig.1
Initial adjustment
Start Operation
1: Refer fig.5 of "■Switching HART Communication Function" for details.
2: Refer "■Operation" for details of operation.
Operating Principle
Operation principle is the same as basic type. Refer Operation manual "SMART POSITIONER
(No.:IP8S-OM00009)".
Mounting
Mounting of IP8001 Smart Positioner is the same as basic type. Refer Operation manual "SMART
POSITIONER (No.:IP8S-OM00009)".
Piping
Piping of IP8001 Smart Positioner is the same as basic type. Refer Operation manual "SMART
POSITIONER (No.:IP8S-OM00009)".
<Perform initial adjustment in the following order along with this manual>
1. Select calibration
mode
2. Check the angle of
the feedback lever
3. Simple balance
current adjustment
4. Calibration
5. Calibration of
input current
Fig. 2
1414
Select the mode used for initial
adjustment.
Check the angle of the feedback
lever.
Adjust balance current simply.
Perform zero point/span adjustment
and PID constant settings suitable
for the connected actuator.
Perform calibration of the input
current as necessary. Normally, this
is not required.