Elsner WS1 Color Manual

Control system for buildings and for conservatories
Hide thumbs Also See for WS1 Color:
Table of Contents

Advertisement

Quick Links

EN
WS1 Color
Control System for Buildings and for Conservatories
WS1 Color 60145, 60135-60138 (white), 60146, 60139-60142 (alu)
WS1000 Color
Control System for Buildings and for Conservatories
WS1000 Color 60121-60124 (white), 60125-60128 (alu)
Manual

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the WS1 Color and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Elsner WS1 Color

  • Page 1 WS1 Color Control System for Buildings and for Conservatories WS1 Color 60145, 60135-60138 (white), 60146, 60139-60142 (alu) WS1000 Color Control System for Buildings and for Conservatories WS1000 Color 60121-60124 (white), 60125-60128 (alu) Manual...
  • Page 3: Table Of Contents

    3.2.4. Adjust ventilation block ..................63 3.2.5. Set night-time re-cooling (ventilation) ............... 63 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Control System WS1 Color / WS1000 Color • from software version 1.817 Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 4 6.1.10.Define channel order ..................97 6.2. WS1 / WS1000 Settings ..............97 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Control System WS1 Color / WS1000 Color • from software version 1.817 Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 5 7.4.2. Use drive outputs for centralised control ............113 7.5. Personal automatic settings data ..........114 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Control System WS1 Color / WS1000 Color • from software version 1.817 Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 6 The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de to find out whether a more up-to-date version of the manual is available.
  • Page 7: Description

    Description 1. Description Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 8: Field Of Application

    For information on installation, maintenance, disposal, scope of delivery and technical data, please refer to the installation instructions. See installation instructions WS1 Color. See installation instructions WS1000 Color. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 9: Connection And Control Options

    Description 1.3. Connection and control options Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 10 • Radio remote control Remo 8/pro, push buttons Corlo P RF, push button interface RF-B2-UP • Elsner ventilation devices (WL400, WL800, WL-Z) Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 11: Automatic Functions In Overview

    If a smoke detector is connected, windows will be opened auto- matically when a fire alarm is triggered. Step windows will be opened step-by-step. An opening position can be set for sliding windows. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 12 (only time-controlled or manual closing) or keep closed regardless of brightness (visual protection, automatic retraction only when there is a rain or wind alarm) • Adjustable movement position Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 13 • Additionally with roof ventilators WL400/800: recirculating air for heat recovery; recirculating air to avoid condensation • Cancel ventilation when cooling/air-conditioning unit is active Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 14 (getting rid of smoke) and heatings and air conditioners switch off. No manual operation is possible. An acoustic warning signal will sound at the control system. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 15: Operation And Use

    Operation and use 2. Operation and use Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 16: Weather Data Display (Starting Image)

    3.3. Set night_time re-cooling (ventilation) 3.3. Adjust frost alarm 3.3. Set movement limitations (windows) Indoor information Temperature in degrees Celsius (°C) Air humidity in %RH Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 17 When there is a precipitation report and temperatures above -3 °C, it is raining. Snow: When there is a precipitation report and temperatures below -3 °C, it is snowing. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 18: The Touch Display

    2.3. Manually operate drives and devices 2.3.1. The „Manual“ menu You can reach the menu for manual control of drives and equipment by using the but- ton Manual: Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 19 Down buttons (for blinds, also the slat position). For radio motor control units, the po- sition shown can deviate from the movement position set in the automatic mode by up to 2%. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 20 Whether a drive or device is in automatic mode or manually operated can be recog- nised from the white marking on the buttons on the right and the text “Auto” next to Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 21: Internal Buttons (Group Buttons)

    In the control, several Remo 8 (pro) devices can be configured.  6.1. Wireless connections Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 22: Navigation In The System Menu

    Back to the previous menu level (only settings already saved with OK will be applied) Back to the weather data display (starting image) Confirms (saves) adjustments made Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 23: Input Keyboard For Names And Codes

    Color intensity 24 bit or 16 bit • No compression (RLE) • The data must be saved in the uppermost level of the card's directory (root directory) Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 24 Further information about the image display can be found in chapter  6.2. Using an SD card Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 25: Automatic Settings

    Automatic settings 3. Automatic settings Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 26: Automatic Settings

    Note that the rails of shutters, awnings and blind which are externally mounted can ice up. Operating the drive under such conditions can damage the shades and drives. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 27: Power Failure, Maintenance Works, Etc. (Restart Of Control)

    Indoor sensor to be used for the awning • Indoor temperature block • Outdoor temperature block • Frost alarm • Wind alarm • Rain alarm • Enable/Disable automatic reset Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 28 For the automatic system to react, the set light intensity value must be exceeded or un- dercut for the duration of the delay times. This prevents constant extensions and re- Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 29 Press the button to set the movement position for the automatic mode. With the arrow keys, specify the movement position in % (0% = fully retracted, 100% = fully extended). Default setting: 75%. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 30 Please note that the shade rails or other mechanical components can remain iced even when the outdoor temperature has already risen to a relatively high value. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 31 Manual menu and press the frost alarm button. If the button is shown normally (black writing), the block has been removed. The block will then be first active for this Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 32 Disable: For internal awnings, select No (awning should not be retracted when it rains, default setting). Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 33: Automatic Blind And Roller Shutter Settings

    Fire alarm of a smoke detector has highest priority. All shades are retracted and can- not be influenced either by automatic or manual operation. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 34 Never. The shading will then only be closed in the night closing and time closing periods set by you. Manual closing is possible. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 35 (the display on the control unit will show "Please set clock!"), the shades will only be controlled based on light intensity, temperature and alarm reports. The positi- on of the sun will not be taken into account. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 36 As soon as the set indoor temperature is exceeded, the block is released and the shade is activated. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 37 Activate one or more periods on the list. The periods can be individually customised (see below). Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 38 Disable block: If the blind respectively the roller shutter should be deployed to offer shade regardless of the outdoor temperature, press the Off button. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 39 Activate: If the sun shade is to be retracted when there is a frost alarm, select Yes. Deactivate: If the sun shade should offer shade regardless of the frost risk, select No (default setting). Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 40 Switching on: To perform an Automatic Reset after a manual intervention, select Yes. Switching off: To switch off the blinds’s/ shutter’s Reset function, select No (this is the default setting). Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 41: Automatic Window Settings

     System > Automatic Settings > General Settings > Ventilation Block  3.3. Adjust ventilation block Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 42 Shutting off ventilation: If ventilation shall be independent of indoor temperature, press the button labelled OFF. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 43 With step windows the control unit checks every 3 minutes whether the set room temperature or air humidity has been exceeded and then moves up another step if necessary. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 44 At the end of a ventilation period, the normal automatic ventilation according to temperature and air humidity will be executed. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 45 Manual operation continues to remain possible, even when the window is blocked be- cause of low outdoor temperatures. Set value: Use the arrow buttons to change the value according to your wish. Default setting: 5.0°C Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 46 Deactivate: If ventilation is to take place via the window regardless of the frost risk, se- lect No (default setting). Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 47 A wind alarm triggered for the drive will be maintained for 5 minutes. If during these 5 minutes the saved value is exceeded again, the holding time begins again. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 48 With the arrow keys, specify the movement position in % (0% = closed, 100% = fully open). Default setting: 5%. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 49: Automatic Ventilation Settings

    In the event of a fire alarm from a smoke detector, ventilation is activated and cannot be influenced by either the automatic or the manual. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 50 Shutting off ventilation: If ventilation is to be independent of indoor temperature, press the button labelled OFF. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 51 Press the button to set the ventilation levels of the motorised roof ventilators. The fur- ther the indoor temperature and air humidity lie above the reference values, the higher the ventilator shifts. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 52 The button is only activated once a night-time re-cooling period has been set. Use the arrow keys to change the value as required. Default setting: 16.0°C. Confirm your setting by pressing OK. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 53 In principle, the recirculation function only starts if the tempe- rature at the ventilator is at least 3° warmer than the indoor temperature. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 54 The button is only active if a night mode operation period has been set. Use the arrow buttons to change the value according to your wish. Default setting: 9.0°C Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 55: Ventilation Modes Wireless Roof Ventilator

    Night mode (period) and indoor night temperature • Enable/Disable automatic reset The automatic heating functions can be accessed by pressing the buttons: Automatic Settings System Air Conditioner Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 56 The heating will engage as soon as the temperature drops below the set value and is shut down again when the temperature is more than 0.5°C above the set value (hyste- resis). Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 57: Automatic Air-Conditioner Settings

    System Air conditioner Now you can select individual air conditioners and adjust their settings. For each air conditioner the following settings can be changed: Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 58 The cooling will engage as soon as the temperature exceeds the set value and is shut down again when the temperature is more than 2°C below the set value (hysteresis). Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 59: Automatic Light Settings

    Activate one or more periods on the list. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 60 Automatic Reset time and/or period can be set.  System > Automatic Settings > General Settings > Automatic Reset  3.3. Define automatic reset Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 61: Automatic Roof Gutter Heating Settings

    Automatic Reset time and/or period can be set.  System > Automatic Settings > General Settings > Automatic Reset  3.3. Define automatic reset Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 62: Set Up Alarm

    Activate one or more periods on the list. The operating times can be individually customised (see below). Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 63: Adjust General Automatic Settings

    Use the arrow keys to set the values for the extension and retraction delays. Default setting: Extension 1 minute, retraction 12 minutes. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 64: Set Timer

    Select the day of the week on which the time period should be activated. More than one day can also be selected. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 65: Adjust Ventilation Block

    Also set the period for which the outdoor temperature must have been above the mi- nimum temperature (e. g. longer than 48 hours). Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 66: Adjust Frost Alarm

    (e.g. 5.0°C) and the duration for which it should be exceeded (e.g. 5 hrs). Choose the time period so that ice is completely melted thereafter. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 67: Set Movement Limitations (Window)

    System Windverzögerung Set the duration of the shade block after a wind alarm using the arrow keys (0-360 mi- nutes, default setting: 0 minutes). Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 68: Define Automatic Reset

    Use the arrow keys to set the time interval after which Automatic functions should be once again activated.Default setting: 60 minutes. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 69: Installation

    Installation 4. Installation Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 70: Procedure

    When planning facilities with devices that communicate via radio, adequate radio re- ception must be guaranteed. The range of wireless control will be limited by legal reg- Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 71: Safety Notice For Automatic And Alarm Functions

    If a power outage occurs, the control unit can no longer control the connected drives! If the functional scope must be guaranteed even during a power cut, an emergency Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 72: Installation Of The Weather Station

    Drives can be kept in secure position by using safety contacts (multifunctional inputs). Take note that a safety contactis not capable of preventing collisions (e.g. if an awning is installed over a window). Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 73: Connect Devices To The Multifunctional Outputs

    A closed contact on the multifunction input can be used to test if a sliding door is closed. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 74: Connecting Drives And Devices Wirelessly

    Please observe the installation instructions relating to the wireless relays, motor control devices and ventilation devic- 6.1. Wireless connections Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 75: Commissioning

    Commissioning 5. Commissioning Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 76: Procedure

    The time is automatically displayed when the unit receives time /date information, oth- erwise, the time can be set manually. Also a time zone (if there is a GPS weather station Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 77: Check Sensor Functions

    The “Precipitation” animation should then be- gin. Please take note that after the sensors dry out, the precipitation warning remains for a further 5 minutes. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 78 Normal values are approx. 25% RH to 65% RH in living rooms. After installation it may be a few hours before the hygrometer shows normal values. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 79: Basic Setting

    Basic Setting 6. Basic Setting Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 80: The "Installation" Menu

    Now you can select individual drives (or drive groups) from the list and adjust their set- tings. So long as no settings were completed yet, the buttons show (Drive 1), (Drive Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 81 Enter the desired name via the keypad that appears.  2.4. Input keyboard for names and codes Confirm your input with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 82 Choose whether the drive should retract (or open) or ex- tend (or close) when the button is pressed. Confirm your selection with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 83 MF inputs. If the safety contact is opened, then the drive will advance to the safe position (window closes, shade retracts) and manual operation is blocked. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 84: Tips On Connecting Windows

    To be able to control a dimmer, the single button must be allocated the function of the  Button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 85 If the direction of the button matches the display, leave the setting at Normal. Otherwise press the button Invert. Now button and display should match. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 86: Assign Internal Buttons (Group Buttons)

    Press the Reserve button. A selection menu appears. Select Int. Button or leave “Re- serve” if the button is not being used for the moment. Confirm your selection with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 87: Set Up Multifunctional Outputs

    If an output was already configured, the function and/or name will be displayed in- stead. Press the button of the output to be set. For each multifunctional output the following settings can be changed: Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 88: Set Up Multifunctionals Inputs

    To the multifunctional inputs you can connect: • alarm signal (motion or smoke detectors) • climate indicators (e.g. a climate/heating unit that is independent of the control Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 89 The settings for the multifunctional inputs can be accessed by pressing the buttons: Installation System Multif. Input Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 90: Wireless Connections

    Some devices have programming keys for learning the radio connection inside their housings. and thus beneath unprotected live parts. •This devices should only be learned by a trained electrician (according to VDE). Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 91: Learn Wireless Connection

    Enter the required name in the box which appears. Confirm your entry using the OK key.  2.4. Input keyboard for names and codes Radio status Radio status display Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 92 Enter the required name in the box which appears. Confirm your entry using the OK key.  2.4. Input keyboard for names and codes Serial number Display of serial number Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 93 Confirm your entry using the OK key.  2.4. Input keyboard for names and codes Display of serial number, version and used rf router if applicable Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 94 Confirm your entry using the OK key.  2.4. Input keyboard for names and codes Radio status Radio status display WL305/610 status Display of serial number, period, flap movements, version Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 95 If "Dimmer" or "None" is selected, the device can be switched on and off only by hand, there are no automatic regime menus. Confirm your entry using the OK key. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 96: Delete Wireless Connection

    Select the wireless participant to be deleted. Confirm the question “Really delete wire- less connection to member XX?” with Yes. The wireless connection is deleted. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 97: Indoor Sensor For Weather Display

    Basic Setting 6.1.7. Indoor sensor for weather display In the weather data display, the values from a sensor (e.g. internal sensor of WS1 Color or wireless sensor WGTH-UP) can be displays. Wireless sensors have to be taught in to the control first.
  • Page 98: Configuring Internal Thermometer/Hygrometer Of Ws1

    Enter the desired name using the key pad that appears. Confirm your selection using OK.  2.4. Input keyboard for names and codes Status Display of status Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 99: Define Channel Order

    • Storing the set-up data for the control system on the SD card or reading the data from the SD card (only WS1000 Color) Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 100: Settings

    WS1 / WS1000 Settings Settings System Language Select the desired language for the menues by pressing the button. Confirm your set- ting with the OK button. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 101: Adjust Screen

    Settings System Time zone The time zone can be set by pressing the arrow keys in the menu that appears. Examples for UTC difference: Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 102: Enter Location (Only Dcf Weather Stations)

    In the menu that appears, you can enter the location as a city or as coordinates (lon- gitude and latitude). City Select City to make a selection under Country and City from a list using the buttons. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 103: Calibrate Touch

    After starting up, all drives and devices with activated automatic reset will be in automatic mode. The Reset function can be accessed by pressing the buttons: WS1 / WS1000 Settings System Service Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 104: Factory Settings

    The access code settings can be accessed by pressing the buttons: WS1 / WS1000 Settings System Access Code Here you can enter, change and delete a code. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 105: Using An Sd Card (Only Ws1000 Color)

    The SD card slot can be found under the covering flap. The SD card is pushed into the slot, until it clicks into place. oder Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 106: Show Images On Display

    Note: The sequence of the catalogue of individual images and of the slideshow corre- sponds to the sequence in which the images were saved onto the card. The images are not sorted according to name. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 107: Saving And Loading Configuration Data

    Confirm by pressing the OK button to save the information.  2.4. Input keyboard for names and codes Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 108 Basic Setting Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 109: Tables, Diagrams, Maintenance

    7. Tables, diagrams, maintenance Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 110: Care And Maintenance

    17,2-20,7 62-74 34-40 Strong gale 20,8-24,4 75-88 41-47 Whole gale 24,5-28,4 89-102 48-55 Storm 28,5-32,6 103-117 56-63 Hurricane > 32,6 > 117 > 63 Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 111: Alarm And Error Messages

    RF868 wireless module faulty! means that the internal wireless module is not working properly. Contact customer ser- vice to have the control unit checked. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 112: Manual" Menu Messages

    The control system has not yet received any data from a configured wireless sensor. Once data is received, the message disappears. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 113: Connection Diagrams

    7.4.1. Connection of several drives to one 230 V drive output Drive group with a total output of less than 500 VA. Motors without integrated group control relay. Drive Output Control system Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 114 Drive group with a total output of more than 500 VA. The possible total output de- pends on the group control relay. Motors without integrated group control relay. Drive Output Control system Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 115: Use Drive Outputs For Centralised Control

    7.4.2. Use drive outputs for centralised control Simple centralised control Example for simple central control with motor-control devices in one drive group of the control system. Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 116: Personal Automatic Settings Data

    Slat position Slat position 0°-15° for height of 15°-30° the sun of 30°-45° 45°-90° Indoor sensor Indoor temperature (°C) Night closure? Timed closure (period) Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 117 Timed ventilation (period) Outdoor temperature (°C) Timed closure (period) Frost alarm? Wind alarm at (m/s), Time exceeded Rain alarm? Gap opening during rain? Position Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 118 (period, temperature) Heat recovery recircula- tion (temperature, step) Condensation air recircu- lation (level) Automatic reset? Reset following manual intervention? Ventilation block via air-conditioning (min) Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 119 (°C), standby (h) Window travel limit (°C) Automatic shading wind delay (min) Time point for general auto- matic reset Reset following manual intervention (min) Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 120 Timer time periods Name from Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
  • Page 122 Questions about the product? You can reach the technical service of Elsner Elektronik under Tel. +49 (0) 70 33 / 30 945-250 or service@elsner-elektronik.de We need the following information to process your service request: • Type of appliance (model name or item number) •...