Air Humidity
Press the button to set the air humidity above which the ventilation will be switched on
at night. Until an indoor sensor is selected, the air humidity will be disregarded.
Setting humidity: Adjust the value for the desired humidity using the arrow buttons.
Pre-setting: 80%.
Shutting off ventilation: If ventilation is to be independent of air humidity, press the
button labelled OFF.
Confirm your setting with the OK button.
CO2
Press the button to set the CO
CO
sensor is selected, the CO
2
Setting CO
: Use the upper arrow keys to set the value from which the ventilation starts
2
at the lowest preset speed. Default: 700 ppm.
Use the lower arrow keys to set the value at which ventilation takes place at the highest
specified speed. Default: 1500 ppm.
The speed is automatically adjusted between the two values.
Shutting off ventilation: If ventilation is to be independent of the CO
Off button.
Confirm your setting with the OK button.
Supply-Air Temp.
Press the button to set the supply air temperature block (summer operation). With WL-
Z supply air units, the supply air temperature is recorded by a thermometer integrated
into the WL-Z. With devices from other manufacturers the outdoor temperature at the
weather station is used as the supply air temperature.
Enable: If the supply air unit should be closed when the supply air temperature is war-
mer than the room temperature, select Yes.
Disable: If the supply air unit should also then be/remain open when the supply air tem-
perature is warmer than the room temperature, select No (default setting).
Confirm your setting with the OK button.
Exhaus Air Levels
Press the button to set the ventilation levels of the motorised roof ventilators. The fur-
ther the indoor temperature and air humidity lie above the reference values, the higher
the ventilator shifts.
Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
49
Humidity Ventil.
For all ventilation units but only if a CO
installed.
content of the room air to be ventilated. As long as no
2
content is not taken into account.
2
Only for WL-Z
and ventilation units at MF output/RF Relay.
Ventilation Levels
Automatic settings
For all ventilation units.
2
Only for air supply on RF-VM.
sensor is
2
content, press the