Elsner WS1000 Connect Installation, Setting, Operation

Building controls
Hide thumbs Also See for WS1000 Connect:
Table of Contents

Advertisement

EN
WS1000 Connect
Building controls
Article numbers 60241-60246
Installation, setting, operation

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the WS1000 Connect and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Elsner WS1000 Connect

  • Page 1 WS1000 Connect Building controls Article numbers 60241-60246 Installation, setting, operation...
  • Page 3: Table Of Contents

    3.3.1. Motors and devices without automatic functions ..........36 3.3.2. Set automatic sun protection ................36 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany WS1000 Connect controls • from software version 1.09 Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 4 5.1. The "Installation" menu ..............70 5.1.1. Set motors and motor groups ................71 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany WS1000 Connect controls • from software version 1.09 Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 5 Connection examples for multifunction outputs ..........105 6.4. Personal automatic settings data ..........106 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany WS1000 Connect controls • from software version 1.09 Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 6 The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service" to find out whether a more up-to- date version of the manual is available.
  • Page 7: Description

    Description 1. Description WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 8: Area/Field Of Application

    1.1. Area/field of application The various technical facilities installed in the building are controlled automatically and operated manually using the WS1000 Connect controls. In order to be able to set up the system flexibly, both cable connections and wireless channels are available.
  • Page 9 - RF-L wireless dimmer: The wireless actuators with a production date after 14.01.2016 are compatible with the WS1000 Connect system. The production date can be found as part of the serial number which has the following structure "DD MM YY consecutive number".
  • Page 10: Overview Of Connection And Control Options

    However, they can be operated manually via the display. Sliding doors do not have automatic functions either. They can be fitted with a To contact (at the multifunction input) and operated manually via the display. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 11 If a smoke detector is connected, awnings are retracted automatically if there is a fire alarm. Automatic functions for blinds: • Close depending on brightness and sun position or keep open irrespective of brightness (closing only time-controlled or WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 12 Automatic functions for heating: • Switch on during the day below a selectable indoor temperature • Lowering at night (period and temperature can be set, to which it should be lowered) WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 13 5 minutes if there is no new alarm signal • Smoke detector: If there is an alarm, shades retract (escape routes), windows open, fans open/switch on (smoke removal) and heating and air-conditioning WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 14: Technical Data, Central Unit Ws1000 Connect

    400 W, Motor outputs total max. 1.5 kW Radio frequency radio chan- 868.2 MHz (Elsner RF). nels The product is compliant with the provisions of EU Directives. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 15: Operation

    Operation 2. Operation WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 16: Start Page

    Operation 2.1. Start page With the WS1000 Connect controls you can control the connected technology cen- trally, e.g. raise and lower shades, switch devices on and off and dim lights. All the set- tings are also made on the display.
  • Page 17: Weather Data Display

    -3 °C it is raining Snow If there is a rain message and there are temperatures below -3 °C it is snowing. Sun data: WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 18  3.3. Set night back cooling (ventilation)  3.3. Adjust frost alarm  3.3. Set movement limit (windows) Indoor data: Temperatures in degrees Celsius (°C) Humidity in %rF WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 19: The Touch Display

    The following groups are available: • Central function: for group keys and scenes • All visible functions: all functions, not selection possible • Room control: for heating, air-conditioning and fans WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 20: Examples Of Manual Pages

    Examples of manual pages Blinds in automatic mode: Sliding bar position Field for Selection info icons Position informa- tion Control buttons WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 21: Key Functions And Display Fields

    Switch lights to automatic mode: Field for Selection info icons Status informa- tion Control buttons Key functions and display fields Up/down keys: The keys Up and Down have a timer automatic. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 22 (key "Auto" or "Automatic reset"). In addition, an automatic reset can be activated in the automatic settings of each motor group and each device, both at a fixed time and after a manual operation. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 23: Info Icons

    Manual operation blocked. Rain alarm! Manual operation blocked. Frost alarm! Manual operation blocked. Block active! E.g. ventilation prevented because of active fire, block as a result of safety contact. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 24 Time opening active Time closing active Retraction and extension delay has not yet expired. Icons for windows/ventilation: CO2 value too high. Ventilation active. Humidity too high. Ventilation active. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 25 Ventilation prevented. Circulation air for heat gain Circulation air for preventing condensation. Icons for light: Twilight/night. Light on. Time switching. Icons for heating: Indoor temperature too low. Heating on. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 26: External Keys

     5.1.4. Funkverbindungen, Page 81 2.4. WS1000 Connect App The WS1000 Connect App is available for Android and iOS free of charge in the re- spective APP store. Install the App on the mobile device. As soon as the mobile device and WS1000 Con- nect are on the same network (WLAN), the WS1000 Connect controls can be con- trolled via the App.
  • Page 27: Navigate In The System Menu

    Operation If you want to operate the controls and your building technology on the go, then use the WS1000 Connect App and set up a secure VPN connection for your home net- work. If two WS1000 Connect controls are installed in one building, so that the App control is possible they have to be connected to different WLAN networks.
  • Page 28: Internet (Browser)

    2.5. Internet (browser) The WS1000 Connect controls includes a browser for accessing internet pages on the WorldWideWeb. Music and video streaming services can therefore also be used.
  • Page 29: Slide Show

    The image changes approx. every 45 seconds (for images with 24-bit colour intensity). To interrupt the screen saver, touch the screen or remove the SD card. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 30 Operation WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 31: Automatic

    Automatic 3. Automatic WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 32: Set-Up Automatic

    Adjust the settings for motors and devices to the individual situations. This is the only way alarm and block functions such as rain or wind warnings can help to protect ex- ternal awnings, for example, or prevent rain entering the window. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 33: Safety Notice For Automatic And Alarm Functions

    If cleaning or maintenance work is to be carried out in the conservatory/building, the control unit should be de-energised and secure against restart by disconnection of the customer-installed fuse. This ensures that the connected drives cannot start. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 34: Adjust General Automatic Settings

    16 periods can be set in the weekly clock, which can be used for different automatic functions. A start and end point, as well as a week of the day must be set for each time period. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 35: Adjust Ventilation Lock (Air-Conditioning Unit)

    Shows the settings for the night back cooling as soon as the back cooling has been set up. Touch the field to perform the configuration. Switch the night back cooling On in order to set up and use for windows / fans. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 36: Adjust Frost Alarm

    First determine when the frost alarm is to be triggered. Use the slider to set the outside temperature which must be undercut in order to trigger the frost alarm. Default: 2.0°C. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 37: Set Movement Limit (Windows)

    For shades, a delay time after the wind alarm can also be set, during which the shade controls is blocked. This means the controls initially remain switched off after the wind WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 38: Specify Automatic Reset

    Devices (e.g. lights) connected via the "Dimming" output do not have automatic functions. However, they can be operated manually via the display. 3.3.2. Set automatic sun protection  System > Set-up automatic > Awning | Blind | Shutters WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 39: Alarm Functions

    Set-up automatic Light intensity: Shows the brightness from which shades are deployed. Touch the field to set the shad- ing. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 40 Shows the actuation position in percent for automatic mode. Touch the field to set the position using a slider. 0% = fully retracted, 100% = fully extended. Default: 75%. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 41  3.2.2. Change travel delay (shades), Page 32 Night closing: Shows whether the shades are extended or not at night. Touch the field and switch the night closing on or off. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 42 Shows the actuation position in percent for the time closing, also the slat position for blinds. Touch the field to set the position using a slider. Actuation position: 0% = fully retracted, 100% = fully extended. Default: 100%. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 43 The shade is raised at the time start of the open time but can still be lowered again manually. After the opening time, the normal automatic shade controls are executed. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 44 Default: 6.0 m/s. If the shade should not react to the wind (e.g. for indoor awnings, shutters), switch the wind alarm OFF. The wind alarm protects sensitive curtains from wind damage by retracting the shades. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 45: Set Automatic Window Controls

    • Wind sensor which is evaluated and delay • Wind alarm • Rain alarm • Gap ventilation • Position during gap ventilation • Frost alarm • Automatic reset WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 46: Alarm Functions

    Touch the field to adjust the indoor temperature. Select OFF if the window should not react to the indoor temperature (default). WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 47 Then every 3 minutes the controls check whether a set room temperature or humidity is still exceeded and then, if applicable, move the window by another step. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 48 Movement limit: Shows whether the movement limit is switched on for lower outside temperatures for this window. Touch the field to change the setting. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 49 Shows the delay for the wind sensor. Touch the field to select the sensor (if there are several wind sensors), and to set how long the wind limit value must be exceeded be- fore the wind alarm is triggered. Default: 5 seconds WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 50 Shows the position to which the window opens for gap ventilation. The setting is only active if gap ventilation has been switched on. Touch the field and set the open position (0% = closed, 100% = fully open). Default: 5%. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 51: Set Automatic Ventilation

    Circulation air for reducing condensation (only roof ventilator WL400/800) • Night back cooling (and indoor temperature for night back cooling) or night mode • Time ventilation (and intensity for time ventilation) WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 52: Alarm Functions

    The setting is only active if an indoor sensor is selected. Touch the field to adjust the indoor temperature. Select OFF if the ventilation should be on irrespective of the indoor temperature. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 53 Default: Start above 1000 ppm, end below 700 ppm. Exhaust air intensity (exhaust units): For exhaust units, shows the speed range for automatic exhaust air. Touch the field and set the start and maximum values. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 54 Shows the indoor temperature, to which room is cooled. Touch the field to set the in- door temperature, until which the ventilation is active during the night back cooling. The setting will only be activated once a night-time re-cooling temperature has been WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 55 For exhaust units, shows whether the winter switching is active. Touch the field to set the outside temperature, above which the ventilation unit should remain closed (winter switching). Default: OFF or 1.0°C. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 56: Ventilation Modes, Radio Roof Fan

    Shows the indoor sensor, which is evaluated for the controls. Touch the field and select a sensor. Default: No sensor. If no sensor is selected, the indoor temperature is not taken into account for the con- trols. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 57: Set Automatic Air-Conditioning

    3.3.6. Set automatic air-conditioning  System > Set-up automatic > Air-conditioning unit For connected cooling/air-conditioning units, you can change the following automatic settings. • Indoor sensor evaluated for the cooling WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 58 2°C below the set value (hysteresis). Automatic reset: Shows which automatic resets apply to this cooling. Touch the field in order to activate the daily automatic reset and/or reset after a manual operation. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 59: Set Automatic Light Controls

    Touch the field and select Yes or No. Automatic reset: Shows which automatic resets apply to these lights. Touch the field in order to activate the daily automatic reset and/or reset after a manual operation. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 60: Set Automatic Gutter Heating

    5 minutes. If the saved value is exceeded in these 5 minutes, the stoppage time will be restarted. • Smoke detector (on a multifunction input) WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 61: Set Motion Detector

     3.3.9. Set alarm > Alarm output, Page 58 Light can also be switched on if there is an alarm from a motion detector.  3.3.7. Set automatic light controls, Page 57 WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 62 Automatic WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 63: Installation And Commissioning

    Installation and commissioning 4. Installation and commissioning WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 64: Procedure

    See manual chapter Automatic. 4.1.1. Operating system The WS1000 Connect works with the Android operating system. However, the con- trols work self-sufficiently and therefore no third-party Apps may be installed! 4.1.2. Protective film Remove the protective film from the display.
  • Page 65: Notes On Wireless Equipment

    Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions.
  • Page 66: Power Failure, Maintenance Works, Etc. (Restart Of Control)

    This ensures that the connected drives cannot start. 4.2. Installation of the weather station: see leaflet 4.3. Installation of the indoor sensor: see leaflet 4.4. Installation of the controls: see leaflet WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 67: Connect Motors And Devices

    The device works at 230 V AC 50 Hz, the power consumption depends on the number and power of the connected motors. For version WS1000 Connect (for 230 V motors) each motor output can be loaded with max. 400 Watts. The total installed power must not exceed approx. 1.5 kW, how- ever.
  • Page 68: Connect Device To Multifunction Inputs

    Connect motors and devices wirelessly with the controls The wireless connection of devices and motors uses the Elsner radio module (e.g. RF relay, RF-MSG motor controls, RF-L dimmer). Elsner Elektronik fans can be taught to the controls without an additional device. Please note the installation instructions en- closed with the radio modules and fans.
  • Page 69: Start Controls

    After installation, cabling and check of all connections, switch on the mains power. The controls start and first of all the model (WS1000 Connect) and operating system (Android) are displayed. When the controls have fully booted, the controls are in the output position with weather data display.
  • Page 70 25% rF to 65% rF in living rooms. After installation, the hygrometer may need several hours before normal values are displayed. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 71: Basic Setting

    Basic setting 5. Basic setting WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 72: The "Installation" Menu

    Allocation to motor groups) • Multifunction output (with the possible settings Type, Name, Display and he manual menu) • Multifunction input (with the possible settings Type, Name, and Status display) WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 73: Set Motors And Motor Groups

    "closed" to the other limit stop. You need the values for the setting "Actuation times" (see below). ATTENTION Rain and wind alarms are deactivated while this menu item is displayed. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 74 The actuation time for can- vas tightening is 1 second. Slat turning (blinds): Shows whether and in what case the slats are turned. Touch the field to set the slat turn. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 75 The contacts are connected to the MF inputs. If the safety contact is open, the motor moves to the safe position (window closes, shades retract) and manual operation is blocked. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 76: Tips On Connecting Windows

    • Reserve (unused) • Heating • Dimmer • Air-conditioning unit • ventilation • Light • Gutter • Alarm You can test the relay function with the key Close. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 77: Set Multifunction Inputs

     6.2. Alarm- und Fehlermeldungen > Rauchalarm, Page 107 A heater or air-conditioning unit (air-conditioning alarm) operated independent- ly of the controls can be connected to a multifunction input with its potential-free relay WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 78: Wireless Connections

    Status of the input: Shows whether the relay is currently open or closed. 5.1.4. Wireless connections Devices, which communicate wirelessly with the controls, first have to be taught to the controls. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 79 Display serial number, version and RF router used Radio Status Displays Radio Status Name Shows the name. Touch the field and enter the desired name using the keyboard that appears. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 80 Touch the field to perform the allocation. If necessary, select the key (right/left). ATTENTION! Only drives/devices that have the same function should be operated together with one key (e.g. only blinds or only windows). WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 81 WL-Z supply air unit: Radio Module Type Display "WL-Z" Display serial number, version and RF router used Radio Status Displays Radio Status WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 82 Relay RF-relay, RF-heating, Heatstrip radiator: Radio Module Type Display "RF-Relay" Display serial number, version and RF router used Radio Status Displays Radio Status WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 83 Display serial number, version and RF router used Radio Status Displays Radio Status Name Shows the name. Touch the field and enter the desired name using the keyboard that appears. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 84 Touch a radio participant and confirm the deletion. Radio activity in the 868.2 MHz band: Shows the radio capacity utilisation The higher the percentage, the more radio traffic on the band. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 85: Allocate External Keys

    Only one device can be allocated to a single key (change/on/off), multiple motors or de- vices can be allocated to a double key (up/down). WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 86: Allocate Internal Keys (Group Keys)

    Shows which motors/devices are allocated to the group key. Touch the field and select the motor groups or a device. ATTENTION Only drives/devices that have the same function should be operated together with one key (e.g. only blinds or only windows). WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 87: Scenes

    5.1.8. Start page Favourites and bookmarks are displayed on the left of the start page. You can set dif- ferent display options here.  System > Installation > Start page WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 88: Manual Page

    All groups are shown in a list. Hold an entry by the list symbol on the right and move it to the desired position. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 89: Weather Data

    Weather display: Shows which sensor is used for the weather data supply on the start page. If several sensors are installed, touch the field to select the desired sensor. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 90: Set Up Ws1000

    Load updates and check the software versions of the controls (device information) 5.2.1. Settings You can make the following settings in the menu area System > Set up WS10000 > Settings: • Time and date WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 91: Enter Time And Date Manually

    Shows the currently selected language. Touch the field to select a different language. Set up screen The WS1000 Connect can display picture file, time/temperature as a screen saver or simple a black screen. The screen saver is activated if the display has not been touched for 5 minutes.
  • Page 92: Switch Key Tone Off/On

    If no command is given for around 1 minute when it is dark, the automatic switch-off darkens the screen again. For the automatic switch-off, the central control unit of the WS1000 Connect con- trols records the brightness. If it is bright in the room, the display lighting is automat- ically switched on.
  • Page 93: Enter Location

    Reset starts the control system software again. The automatic settings are retained. Af- ter starting, the motors and devices, for which an automatic reset is set, are in auto- matic mode. Reset: Touch the key to restart the controls. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 94: Factory Settings

    Touch the field to open the software. Follow the instructions. To create the connection, the device ID of the WS1000 Connect must be input at the PC used for the remote maintenance. Then every menu and function of the WS1000 Connect can be viewed and controlled from the PC.
  • Page 95: Access Code

    App is installed and is connected to the same WLAN. Access with access code allows App operation of the controls only after a code has been entered. Enter the desired PIN number. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 96: Using An Sd Card

    Basic setting 5.2.4. Using an SD card The WS1000 Connect controls can load data from a micro SD card. The SD card storage is needed for: • Screen saver data • Update files for software updates • Saving settings (configuration file) The card socket is located on the right-hand side of the device.
  • Page 97: Show Pictures On The Display

    Basic setting Show pictures on the display The WS1000 Connect can display digitally saved picture data as a slide show or a single image. The picture data for this must be saved on an SD card. Information about possible picture information can be found in chapter Set up screen, Page 89.
  • Page 98: Device Information

    Device information The software for the WS1000 Connect controls can be updated during normal op- eration. If the control is connected to the internet, the control downloads updates au- tomatically after confirmation. Alternatively, you load the new software from the Els- ner Elektronik website and save it to the SD card.
  • Page 99: Tables, Plans, Maintenance

    Tables, plans, maintenance 6. Tables, plans, maintenance WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 100: Maintenance And Care

    Observe the response of the awning or blinds or the window to wind and then correct the wind value accordingly. The following table should make it easier to find the optimal values for your situation: WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 101: Alarm And Error Messages

    After 5 minutes without a new signal from the motion detector, the display disappears and the controls switch the windows to the normal automatic mode again. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 102 (precipitation at low outside temperatures).  3.2.6. Frostalarm anpassen, Page 34 Night back cooling is displayed while night back cooling is active.  3.2.5. Nachtrückkühlung einstellen (Lüftung), Page 33 WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 103: Smoke Alarm

    For motors and devices without a wind, rain or frost alarm, manual operation in the menu Manual remains possible. Motors that react to wind, rain or frost alarms move to the safe position. WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 104 Only use emergency mode briefly in order to position drives manually and then switch it off again. • Emergency mode also remains active if weather data is received again. Switch it off again manually! WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 105: Wiring Diagrams

    Tables, plans, maintenance 6.3. Wiring diagrams Motor and MF outputs: WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 106 Tables, plans, maintenance Inputs: WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 107: Connection Examples For Multifunction Outputs

    Tables, plans, maintenance Connection examples for multifunction outputs 230 V consumers at MF outputs: MF Output 1 MF Output 2 MF Output 3 MF Output 4 Neutre WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 108: Personal Automatic Settings Data

    / alarm Thermostat replacement (on-site) 6.4. Personal automatic settings data Awnings, blinds, shutters Drive no. (output) Name Function Light intensity (kLUx) Direction of sun Height of sun Movement position WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 109 Normal, sliding window or step window? Indoor sensor Indoor temperature (°C) Air humidity (%) CO2 (ppm) Supply air temperature block Night-time re-cooling (period, temp., position) Movement position/num- ber of steps WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 110 Supply air temperature block Exhaust air levels Night-time re-cooling ven- til. (period, temperature) Timed ventil. /Night mode (period, temperature) Heat recovery recircula- tion (temperature, step) Condensation air recircu- lation (level) WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 111 On at alarm? Automatic reset? Reset following manual intervention? General settings Twilight value (Lux) Extension delay shades (min) Retraction delay shades (min) Ventilation block after cool- ing (min) WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 112 (°C), standby (h) Window travel limit (°C) Automatic shading wind delay (min) Time point for general auto- matic reset Reset following manual intervention (min) Timer time periods Name from WS1000 Connect controls • Version: 15.07.2019 • Technical changes and errors excepted.
  • Page 114 Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone +49 (0) 70 33 / 30 945-0 info@elsner-elektronik.de Germany +49 (0) 70 33 / 30 945-20 www.elsner-elektronik.de Technical support: +49 (0) 70 33 / 30 945-250...