Elsner WS1 Color Installation And Operation Manual

Control system for buildings and for conservatories
Hide thumbs Also See for WS1 Color:
Table of Contents

Advertisement

Quick Links

EN
WS1 Color
Control System for Buildings and for Conservatories
WS1000 Color
Control System for Buildings and for Conservatories
including WS1Color-PF and WS1000Color-PF
Installation and Operation

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the WS1 Color and is the answer not in the manual?

Questions and answers

Summary of Contents for Elsner WS1 Color

  • Page 1 WS1 Color Control System for Buildings and for Conservatories WS1000 Color Control System for Buildings and for Conservatories including WS1Color-PF and WS1000Color-PF Installation and Operation...
  • Page 2: Table Of Contents

    3.3.4. Adjust ventilation block ..................62 3.3.5. Set night-time re-cooling (ventilation) ............... 63 Elsner Elektronik GmbH • Herdweg 7 • D-75391 Gechingen • Germany Control System WS1 Color / WS1000 Color • from software version 1.705 Status: 19.11.2012 • Subject to technical changes. Errors excepted.
  • Page 3 Connect devices to the multifunctional inputs ........... 88 Connecting drives and devices wirelessly ............89 Elsner Elektronik GmbH • Herdweg 7 • D-75391 Gechingen • Germany Control System WS1 Color / WS1000 Color • from software version 1.705 Status: 19.11.2012 • Subject to technical changes. Errors excepted.
  • Page 4 7.1. Care and maintenance ..............124 Maintenance of the weather station ..............124 Elsner Elektronik GmbH • Herdweg 7 • D-75391 Gechingen • Germany Control System WS1 Color / WS1000 Color • from software version 1.705 Status: 19.11.2012 • Subject to technical changes. Errors excepted.
  • Page 5 Centralised control with IMSG-UC Motor Control Units ......... 138 7.5. Personal automatic settings data ..........139 Elsner Elektronik GmbH • Herdweg 7 • D-75391 Gechingen • Germany Control System WS1 Color / WS1000 Color • from software version 1.705 Status: 19.11.2012 • Subject to technical changes. Errors excepted.
  • Page 6 (software version and date) can be found in the footer of the contents. If you have got a device with a more recent software version, please have a look at www.elsner-elektronik.de in the „Service“ menu, if there is a more current version of the manual available.
  • Page 7 Explanation of symbols...
  • Page 8: Description

    Description 1. Description Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 9: Field Of Application

    Additionally with WS1000 Color: • WGTH-UP indoor sensor with frame (You need a socket ø 60 mm, 42 mm deep additionally) • Stylus Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 10: Connection And Control Options

    Description 1.2. Connection and control options Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 11 • Radio remote control Remo 8 • Elsner ventilation devices (WL610, WL305, WFL) Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 12: Automatic Functions In Overview

    If a smoke detector is connected, windows will be opened auto- matically when a fire alarm is triggered. Step windows will be opened step-by-step. An opening position can be set for sliding windows. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 13 (visual protection, automatic retraction only when there is a rain or wind alarm) • Adjustable movement position Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 14 Additionally with roof ventilators WL610 and WL305: recirculating air for heat recovery; recirculating air to avoid condensation • Cancel ventilation when cooling/air-conditioning unit is active Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 15 (getting rid of smoke) and heatings and air conditioners switch off. No manual operation is possible. An acoustic warning signal will sound at the control system. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 16: Operation And Use

    Operation and use 2. Operation and use Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 17: Weather Data Display (Starting Image)

    3.3. Set night_time re-cooling (ventilation) 3.3. Adjust frost alarm 3.3. Set movement limitations (windows) Indoor information Temperature in degrees Celsius (°C) Air humidity in %RH Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 18 When there is a precipitation report and temperatures above -3 °C, it is raining. Snow: When there is a precipitation report and temperatures below -3 °C, it is snowing. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 19: The Touch Display

    A stylus is enclosed with the WS1000 control system. It can be stored in the tray be- neath the covering lid. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 20: Manually Operate Drives And Devices

    For shades and windows, the movement position is shown in percent above the Up-/ Down buttons (for blinds, also the slat position). For radio motor control units, the po- Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 21: External Buttons

    (wall buttons) to the control unit. In the System menu the individual buttons can be assigned to any drives or devices.  System > Installation > Ext. Buttons  6.1. Assign external buttons Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 22: Internal Buttons (Group Buttons)

    Define the order in which the drives and devices are shown (e.g. in the manual menu) Automatic settings: • Define automatic functions for the individual drives and devices Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 23: Input Keyboard For Names And Codes

    Selects the input keyboard for letters and numbers. & Selects the input keyboard for symbols and umlauts.  Delete. Removes the preceding character. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 24: Slideshow

    Further information about the image display can be found in chapter  6.2. Using an SD card Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 25 Operation and use Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 26: Automatic Settings

    Automatic settings 3. Automatic settings Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 27: Automatic Settings

    Settings saved in the control unit programme will be maintained even during a power outage. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 28: Automatic Settings For Drive Groups And Devices

    Fire alarm of a smoke detector has highest priority. All awnings are retracted and can- not be influenced either by automatic or manual. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 29 Direction of sun Press the button to set the range (sun direction) in which the sun shall be, so that the awning provides shade. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 30 (Pre-setting: Internal sensor at WS1, first sensor in the list at WS1000). As long as “No Sensor” is selected, the indoor temperature will not be taken into account by the con- trol system for this shade. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 31 Disable block: If the awning should be deployed to offer shade regardless of the out- door temperature (for example with internal awnings), press the Off button. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 32 Wind Alarm Press the button to set the wind alarm. The wind alarm protects the sensitive awning cloth from damage by retracting the awning. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 33 Automatic Reset time and/or period can be set.  System > Automatic Settings > General Settings > Automatic Reset  3.3. Define automatic reset Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 34: Automatic Blind And Roller Shutter Settings

    Setting of the automatic The automatic blind functions can be accessed by pressing the buttons: Automatic settings System Blind Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 35 Enter angle: To set the range in which shading shall be provided in exact numbers, press the “from 0°” or “to 360°” and adjust the numeric values with the arrows keys that appear. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 36 Default setting: 0° to 15°: 100% (closed), 15° to 30°: 80%, 30° to 45°: 65%, 45° to 90°: 50% (horizontal). Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 37  System > Automatic Settings > General Settings > Twilight  3.3. Adjust twilight value Note to night closing function and outdoor temperature block: Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 38 Default setting: 5.0 °C. The block is countermanded again when the tem- Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 39 Activate: If the sun shade is to be retracted when there is a frost alarm, select Yes. Deactivate: If the sun shade should offer shade regardless of the frost risk, select No (default setting). Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 40 Switching on: To perform an Automatic Reset after a manual intervention, select Yes. Switching off: To switch off the blinds’s/ shutter’s Reset function, select No (this is the default setting). Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 41: Automatic Window Settings

     System > Automatic Settings > General Settings > Ventilation Block  3.3. Adjust ventilation block Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 42 Shutting off ventilation: If ventilation shall be independent of indoor temperature, press the button labelled OFF. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 43 With step windows the control unit checks every 3 minutes whether the set room temperature or air humidity has been exceeded and then moves up another step if necessary. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 44 At the end of a ventilation period, the normal automatic ventilation according to temperature and air humidity will be ex- ecuted. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 45 Manual operation continues to remain possible, even when the window is blocked be- cause of low outdoor temperatures. Set value: Use the arrow buttons to change the value according to your wish. Default setting: 5.0°C Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 46 Deactivate: If ventilation is to take place via the window regardless of the frost risk, se- lect No (default setting). Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 47 Disable: If the window should be completely closed when there is rain, select No (de- fault setting). Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 48: Automatic Ventilation Settings

    Indoor temperature • Air humidity • Air supply temperature (only for air supply devices) • Exhaust air levels (only for roof ventilators WL610/WL305) Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 49 Air Supply Unit WFL, ventioaltor at multifunctional output or RF Relay: The ventilation Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 50 Use the arrow buttons to change the start and maximum values according to your wishes. Default setting: Start with level 1, maximum level 8 (full level utilisation). Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 51 However supply air flaps are only opened if the set out- door temperature is hit. Activate one or more periods on the list. Confirm your setting by pressing OK. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 52 Default setting: U-value 1.0; with Level 3. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 53 Switching off: To switch off the ventilation unit’s Reset function, select No (this is the default setting). Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 54: Automatic Heating Settings

    The heating will engage as soon as the temperature drops below the set value and is shut down again when the temperature is more than 0.5°C above the set value (hyster- esis). Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 55 Automatic Reset time and/or period can be set.  System > Automatic Settings > General Settings > Automatic Reset  3.3. Define automatic reset Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 56: Automatic Air-Conditioner Settings

    The cooling will engage as soon as the temperature exceeds the set value and is shut down again when the temperature is more than 2°C below the set value (hysteresis). Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 57 Automatic Reset time and/or period can be set.  System > Automatic Settings > General Settings > Automatic Reset  3.3. Define automatic reset Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 58: Automatic Light Settings

    Enable: If the lighting should be switched on automatically when an alarm is triggered, select Yes. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 59: Automatic Roof Gutter Heating Settings

    If the temperatures are very cold, no condensate forms and the heating can remain switched off. Default setting: 5.0°C to -5.0°C. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 60: Set Up Alarm

    • Frost alarm of the control Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 61: Setting Motion Detectors

    The twilight settings can be accessed by pressing the buttons: Automatic General Settings Settings System Twilight Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 62: Adjust Movement Delays (Shading Elements)

    A start and end point, as well as a day of the week must be set for each time period. The timer settings can be accessed by pressing the buttons: Automatic General Settings Settings System Timer Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 63: Adjust Ventilation Block

    You can adjust the delay time for this. The ventilation block is also iniciated by devices that are connected to the multifunc- tion input as climate signallers. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 64: Set Night-Time Re-Cooling (Ventilation)

    It is a maximum of one third of the set trig- ger period (e.g. max. 12 hours for a 48-hour trigger period). Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 65: Adjust Frost Alarm

    Choose the time period so that ice is completely melted thereafter. The Off button lets you deactivate the frost alarm for all shades and windows. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 66: Set Movement Limitations (Window)

    Set the duration of the shade block after a wind alarm using the arrow keys (0-360 min- utes, default setting: 0 minutes). Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 67: Define Automatic Reset

    Use the arrow keys to set the time interval after which Automatic functions should be once again activated.Default setting: 60 minutes. Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 68: Installation

    Installation 4. Installation Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 69: Procedure

    Elsner Elektronik does not assume any liability for changes in standards after publica- tion of this instruction manual. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 70: Notes On Wireless Equipment

    If the functional scope must be guaranteed even during a power cut, an emergency power unit with a corresponding switch from network power to emergency operation should be installed by the customer. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 71: Installation Of The P03I-Gps Weather Station

    Magnetic fields, transmitters and interfering fields from electricity consumers (e.g. flu- orescent lamps, neon signs, switched-mode power supplies etc.) can interfere with or even cut out reception of the GPS signal. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 72: Preparation Of The Weather Station

    The power supply cable to the weather station should be a maximum of 300 m long. The connection is made with a standard, UV-resistant telephone cable (A-2Y(L)2Y 2x2x0.6 or A-2Y(L)2Y 2x2x0.8). Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 73: Layout Of The Circuit Board

    Check that the lid and lower section have properly latched into place! The diagram shows the closed weather station from be- low. Fastening Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 74: Installation Notes For The Weather Station

    Several separate WGTH-UP can be taught to one control system. The teaching is described in the chapter “Learn wireless connections” (manual of the con- trol system). Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 75: Installation Of The Indoor Sensor

    (see manual chapter on Wireless connections > Status). The indoor sensor must only be installed and used in dry, interior spaces. Avoid condensation. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 76: Layout

    Position the frame of the switching programme. Insert the housing of the sensor firmly onto the base plate using the catches, so that the housing and frame are fixed together. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 77: Notes On Mounting And Commissioning

    Preparing the installation location The device must only be installed and used in dry, interior spaces. Avoid condensation. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 78: Preparing For Installation

    M16 conduit, 50 cm in length 50 cm in length Preparing for installation To take off the front plate, remove the screws beneath the lid. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 79: Wall-Fitting

    It may never be exposed to dust or moisture! For fitting, screw the cover (board) on to the concealed box with the en- closed screws. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 80: Cavity Wall Fitting

    Screw on the upper section. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 81: Structure Of The Connector Board Ws1000 Color

    Wall button 3 (terminals 7-9) and No. 23, term. 3(+), 4(-) | 6(+), 7(-)), Wall button 4 (terminals 10-12) max. 400 mA altogether. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 82: Structure Of The Connector Board Ws1000 Color-Pf

    4.4.2. Installation of the control unit WS1 Color Warning, mains voltage! National legal regulations are to be observed. Installa- tion, inspection, commissioning and troubleshooting of the device must only be Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 83 (antenna dimensions approx. 565 x 8 x 5, L × W × H in mm): Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 84 You can press your thumbs on the screen while doing this. Take the frame off at the top first, then at the bottom. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 85 It may never be exposed to dust or moisture! Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 86 To this end, the frame is first suspended below and then clapped shut above and snapped in place. Structure of the connector board WS1 Color Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 87 Multifunctional output 1 (No. 2, terminal 3(+), 4(-) and (potential-free) No. 3, terminal 6(+), 7(-)), 10 MF output 2 (potential-free) max. 50 mA altogether. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 88: Structure Of The Connector Board Ws1 Color-Pf

    Drives can be kept in secure position by using safety contacts (multifunctional inputs). Take note that a safety contactis not capable of preventing collisions (e.g. if an awning is installed over a window). Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 89: Connect Devices To The Multifunctional Outputs

    Through the closed re- lay, the device signals the control that it is currently heating or cooling and the control activates the ventilation block. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 90: Connecting Drives And Devices Wirelessly

    Please observe the installation instructions relating to the wireless relays, motor control devices and ventilation devic- 6.1. Wireless connections Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 91 Installation Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 92: Commissioning

    Commissioning 5. Commissioning Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 93: Procedure

    The time is automatically displayed when the unit receives time /date information, oth- erwise, the time can be set manually. Also a time zone (if there is a GPS weather station Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 94: Check Sensor Functions

    The “Precipitation” animation should then be- gin. Please take note that after the sensors dry out, the precipitation warning remains for a further 5 minutes. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 95 Normal values are approx. 25% RH to 65% RH in living rooms. After installation it may be a few hours before the hygrometer shows normal values. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 96: Basic Setting

    Basic Setting 6. Basic Setting Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 97: The "Installation" Menu

    The basic settings for the drives can be accessed by pressing the buttons: Installation System Drive Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 98 Press the buttons with the number values and enter the timed values (see top “Drive type”) via the keypad that appears. Confirm with the OK button. Settings Different option settings appear here depending on the drive type: Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 99 The drive time for canvas tightening is 1 second. Confirm your selection with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 100: Tips On Connecting Windows

    In this, the control unit checks the room temperature every 3 minutes. If the temperature is close to the reference value, the window will be opened or closed Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 101: Assign External Buttons

    Button 2) etc. If a button was already configured, the name or function will appear in- stead. Press the key of the button to be set. For each external button the following settings can be changed: Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 102: Assign Internal Buttons (Group Buttons)

    Several drives or devices can be operated at the same time in the Manual menu via a collective group button (internal software button). Ten internal buttons are available. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 103 OK button. Only drives/devices with the same functions should be operated together with a single button (e.g. only blinds or only windows). Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 104: Set Up Multifunctional Outputs

    Press the button to change the name. Enter the desired name via the keypad that ap- pears.  2.4. Input keyboard for names and codes Confirm your input with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 105: Set Up Multifunctionals Inputs

    If cameras are connected to the control system, the setting Binary Input can be used to activate the image display. For example, the signal can be connected to a bell on a Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 106: Wireless Connections

    These wireless actors include WGTH-UP Indoor Sensors, Remo 8 Remote Controls, the Elsner ventilation units (WL610, WL305, WFL), RF-VM Ventilation Mod- ules, RF Relay Wireless Switches or RF MSG Motor Control Units. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 107: Learn Wireless Connection

    Later the names given are shown on the buttons. Different operational data will be shown for the devices: Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 108 Enter the required name in the box which appears. Confirm your entry using the OK key.  2.4. Input keyboard for names and codes Serial number Display of serial number Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 109 Press the Manual Menu button to set if the vent shall be displayed in the manual menu. Confirm your choice using the OK key. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 110 To set what shall be connected to the RF-MSG relay, press the button. Select type of automatic regime (awn- ing, window, sky roof, blinds). Confirm your entry using the OK key. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 111: Delete Wireless Connection

    Press the button to reach the selection menu with the sensors. Then press the button of the desired sensor and confirm using the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 112: Settings For Communication With Knx (Ws1000 Only)

    The KNX drives and devices appear in the menu for Automatic Setting. The setting op- tions for automatic functions are the same as for directly connected drives and devices. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 113: Setting Camera Inputs

    ("Camera interface defect"). By de-activating the interface the er- Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 114: Configuring Internal Thermometer/Hygrometer Of Ws1

    Here all configured drives and devices (“channels”) are displayed. Note that the list also includes those channels that do not appear in the manual menu. The display in the Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 115: Ws1 / Ws1000 Settings

    If no time signal is available, “Please set clock!” will show permanently in the display. While this is being displayed, no weather animations can be shown. In this case, you should set the clock by hand. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 116: Change Language

    If the automatic switcht-off is set to On, the display lighting will be turned off if no com- mand is given for 5 minutes. If the screen is touched, it re-activates. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 117: Select Time Zone

    Europe, USA, None (if no summertime switch-over shall take place) or User-defined (if the switching shall be set individually). Confirm your setting with the OK button. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 118: Enter Location (Only Dcf Weather Stations)

    In the menu area System > WS1 / WS1000 Settings > Service you can adjust the following settings: • Reset (new start) • Factory settings • Internal area Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 119: Reset (New Start)

    “Installation” and “Automatic Settings” menus against unauthorised changes. Manual operation of the control system remains possible at any time. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 120: Using An Sd Card (Only Ws1000 Color)

    The WS1000 Color control system has an SD card slot, which can be used to show the images on the display and to store or transfer the set-up data to the control system. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 121: Show Images On Display

    To return to the weather data display, touch the screen or remove the SD card (briefly press down on the card so that it pops out). Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 122: Saving And Loading Configuration Data

    (max. 7 characters). Confirm by pressing the OK button to save the information.  2.4. Input keyboard for names and codes Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 123 Basic Setting Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 124: Tables, Diagrams, Maintenance

    7. Tables, diagrams, maintenance Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 125: Care And Maintenance

    Stand-by max. 10 W Frequency 868.2 MHz wireless channels Measurement range -40…+100°C temperature Resolution (temperature) 0.1°C Measurement range 0…100% rH humidity Resolution (humidity) 0.3% Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 126: Technical Specifications Control Unit Ws1000 Color

    Colour White / translucent Mounting On-wall Protection category IP 44 Dimensions approx. 96 x 77 x 118 (W x H x D, mm) Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 127: Technical Specifications Wgth-Up

    95% rH, avoid condensation Operating voltage 7…30 V DC Current max. 35 mA Data output Wireless Wireless frequency 868.2 MHz Protocol Proprietary protocol (Elsner RF) Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 128: Units For Sun And Wind

    62-74 34-40 Strong gale 20,8-24,4 75-88 41-47 Whole gale 24,5-28,4 89-102 48-55 Storm 28,5-32,6 103-117 56-63 Hurricane > 32,6 > 117 > 63 Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 129: Alarm And Error Messages

    RF868 wireless module faulty! means that the internal wireless module is not working properly. Contact customer service to have the control unit checked. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 130: Manual" Menu Messages

    The control system has not yet received any data from a configured sensor (wireless or KNX) or KNX actuator. Once data is received, the message disappears. Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 131: Connection Diagrams

    7.4. Connection diagrams 7.4.1. Diagrams WS1 Drive and MF outputs WS1: Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 132 Drive and MF outputs WS1-PF: Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 133 Inputs WS1 and WS1-PF: Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 134: Diagrams Ws1000

    7.4.2. Diagrams WS1000 Drive and MF outputs WS1000: Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 135 Drive and MF outputs WS1000-PF: Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 136 Inputs WS1000 and WS1000-PF: Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 137: Connection Of Several Drives To One 230 V Drive Output

    7.4.3. Connection of several drives to one 230 V drive output Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 138: Use Drive Outputs For Centralised Control

    Example of central control with group formation with motor-control devices in one drive group of the control system: IMSG230 motor-control devices with Up/Down but- tons for manual operation on the spot Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 139: Centralised Control With Imsg-Uc Motor Control Units

    Centralised control with IMSG-UC Motor Control Units Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 140: Personal Automatic Settings Data

    Wind alarm at (m/s), Time exceeded Rain alarm? Automatic reset? Reset following manual intervention? Extension delay (min) Retraction delay (min) Twilight value (lux) Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 141 Ventilation, heating and cooling units No. (output) Name Indoor sensor Air humidity (%) Indoor Temperature (°C) Outdoor Temperature (°C) Supply air temperature block Exhaust air levels Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 142 Automatic reset? Reset following manual intervention? Light No. (output) Name Twilight operation Time switch (period) On at alarm? Automatic reset? Reset following manual intervention? Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 143 General settings Time point for general automatic reset Reset following manual intervention (min) Timer time periods Name from Control System WS1 Color / WS1000 Color • Status: 19.11.2012 • Errors excepted. Subject to technical changes.
  • Page 144 Elsner Elektronik GmbH Control and Automation Technology Herdweg 7 D – 75391 Gechingen Phone +49 (0) 70 56 / 93 97-0 info@elsner-elektronik.de Germany +49 (0) 70 56 / 93 97-20 www.elsner-elektronik.de...

This manual is also suitable for:

Ws1000 color

Table of Contents