The device works with 230 V alternating voltage 50 Hz. The input power is dependent
on the number and power of the connected motors.
Each drive outlet must have a maximum 400-watt load. The total installed input must
not however exceed approx. 1.5 kW. The output voltage is 230 V AC.
When motors are connected in parallel, take note of whether a group control relay is
prescribed by the manufacturer. Group control relays can be obtained from Elsner El-
ektronik or the motor manufacturer.
Various drives for blinds and awnings, in particular, can for the most part only be op-
erated via a group control relay on an output channel.
If motors are connected in parallel which are unsuitable for this
purpose, both they and the control unit will be damaged.
Motors with a higher power input than 400 Watt are to be operated via a relay or con-
trol gate with its own power cable.
For D.C. drives we offer appropriate power supply units. In case of need we ask for de-
tails of the motor type, the manufacturer and – if available – the technical data.
Connect devices to the multifunctional outputs
Heatings, air-conditioners, lights, ventilation devices, roof gutter heatings, dimmers or
alarm devices (e.g. alarm equipment in combination with a motion detector in a mul-
tifunctional input) can be connected to the multifunctional outputs.
The multifunctional outputs have a potential-free make contact which can be loaded
with 230 V AC/2 A.
Connect devices to the multifunctional inputs
Devices with potential-free contacts can be connected to the multifunctional inputs.
These can be alarm-reporting devices, such as motion-detectors or smoke detectors
(with relay output) or another device with a potential-free contact, which is then crucial
for the alarm function.
A smoke alarm at the multi-functional input does not fulfil the
requirements for a smoke alarm system.
A heating or cooling plant operated independently of the control system can be con-
nected to a multifunction input using its potential-free contact. Through the closed re-
lay, the device signals the control that it is currently heating or cooling and the control
activates the ventilation block.
A closed contact on the multifunction input can be used to test if a sliding door is
closed.
Control System WS1 Color / WS1000 Color • Version: 29.07.2024 • Technical changes and errors excepted.
71
Installation
Need help?