6.6.1
Li-Ion Battery Connection
Battery connection diagram
Note: Please be careful of any electric shock or chemical hazards. For batteries without a built-in
DC breaker, make sure that an external DC breaker (≥125A) connected.
The battery used with the inverter shall be approved by the inverter manufacturer. This
inverter can only be connected with LIVOLTEK or Pylontech low-voltage lithium
batteries with nominal voltage from 40V to 60V now. If you choose other lithium
batteries, please consult LIVOLTEK for compatibility. Otherwise, the inverter will not
work normally.
For safe operation and compliance, a two-pole DC circuit breaker with overcurrent
protection should be installed between the inverter and the battery.
If you do not have battery now, you can float BAT terminal, and this hybrid inverter will
only work like a PV inverter.
NOTICE
37