Omron V7-IP65 User Manual page 113

Compact sensorless vector inverter
Hide thumbs Also See for V7-IP65:
Table of Contents

Advertisement

If n045 > 0 the frequency reference is changed in steps of n045 value
Fref
S6
S7
For n045=0, acceleration / deceleration rate is selected by n046:
n046 = 0: Accel/Decel time 1 time (n019 / n020)
n046 = 1: Accel/Decel time 4 (n043 / n044)
Fref
S6
S7
Saving of the Up/Down 2 bias to the EEPROM if save mode n100=1 is
selected (Frequency reference has to remain for 5 sec)
n100 = 1
Fref
S6
S7
112
n045
Acceleration rate,
sel. by n046
5 sec
Up 2/Down 2 bias is not saved,
when Run signal is removed
Reference changes
according to setting in n045
Deceleration rate,
sel. by n046
Up 2/Down 2 bias is saved,
when Run signal is removed
5 sec

Advertisement

Table of Contents
loading

This manual is also suitable for:

Varispeed v7 ip65

Table of Contents