Example: Writing Constants from EEPROM in Operator to Inverter
Explanation
• Enable the set-
tings for con-
stants n001 to
n179.
• Execute write-
in (COPY)
using the Con-
stant Copy
Function
Selection
(n176).
A setting range check and matching check for the written constants are
executed after the constants are written from the Digital Operator to the
Inverter. If a constant error is found, the written constants are discarded
and the constants stored before writing are restored.
When a setting range error is found, the constant number where an error
occurs is indicated by flashing.
When an inconsistency in the settings is found,
is indicated by flashing.
• Press
and
DSPL
PRGM
will light.
• Press
to dis-
ENTER
play the set value.
• Change the set value to 4
by pressing the
key.
• Press
.
ENTER
• Change the constant No.
to n176 by pressing the
or
key.
• Press
to dis-
ENTER
play the set value.
• Change the set value to
CPy by pressing the
key.
• Press
.
ENTER
• Press
or
DSPL
.
ENTER
6 Programming Features
Operator Display
(May be a different constant number)
(Lit)
(May be a different set value.)
(Flashes)
or
(Lit for one second.)
(The constant number is displayed.)
(Lit)
(Lit)
or
(Flashes while executing the
copy.)
(End is displayed after the
copy has been completed.)
(The constant number is displayed.)
( : a number)