Section 7 System Settings
NS-Designer Operation Manual

7-1 Settings

7-1-1

Common Procedure

Select Settings - System Setting. The System Setting Dialog Box will be displayed.
7-1-2

PT Operations

Click the PT Tab.
No.
Setting
1
Startup Wait Time
2
Key Press Sound
3
Buzzer Sound
4
Screen Saver
Screen Saver
Movement
Screen Saver
Startup Time
5
Device Monitor
Changing Value
1
2
3
4
5
6
Set the time required before the PT starts communicating with external de-
vices after turning ON the power or resetting the PT. The startup waiting time
can be set to between 0 and 10 (unit: s).
Select whether an input sound will be heard when an object is pressed.
ON: Input sound enabled
OFF: Input sound disabled
Select whether a buzzer will be heard.
ON:
The buzzer is enabled at the following times:
When system memory bits $SB12 to $SB14 are ON
When an error occurs in the PT
When a message is displayed for the "×" and "!" icons
OFF:
The buzzer is disabled
ERROR ON: The buzzer is enabled at the following times:
When an error occurs in the PT
When a message is displayed for the "×" and "!" icons
Set the various screen saver settings.
Select one of the following screen saver operations.
Display Erased: Erases the screen when it is idle for a specified time.
OFF:
Disables the screen saver.
Set the amount of time after which the screen saver will start up. The time
can be set to between 1 and 255 (unit: s).
Set whether to enable or disable changing monitor values for addresses
displayed on the device monitor screen on the PT.
Enable: Monitor value can be changed.
Disable: Monitor value cannot be changed.