Section 10 Transferring Data
NS-Designer Operation Manual
10. Input the IP address of the PLC's Ethernet Unit. Here, 192.168.0.6 is set for the IP Address as an
example.
11. Click the OK Button in the Network Settings Dialog Box.
12. Click the Set... Button on the right of the NS and PLC Field. The Serial Setting Dialog Box shown
below will be displayed.
13. Set the serial communications network address (the value set for the local network table in the
CX-Net) between the PT and PLC. Set 3 as the Serial communications network address.
14. Set the unit number of the destination PT. Here, 0 is set because the RS-232C port is connected
1:1.
15. Click the OK Button in the Serial Setting Dialog Box.
16. Click the OK Button in the Comms Method Dialog Box.
Set the serial communications network address
(the value set for the local network table in the
CX-Net) between the PT and PLC.
Input the unit number of the PT that is the
target of the 1:N NT Link.
10-47
10-3 Data Transfer Using SPMA
Set the IP address of the PLC's
Ethernet Unit.