Section 10 Transferring Data
NS-Designer Operation Manual
■ Ethernet between a Computer and a PLC and Controller Link between
a PLC and a PT Set for Transferring Data to the PT through the PLC
NS-Designer
NS-Designer IP
192.168.1.0
Address on the
computer
Network Address
1
Node Address
0
Settings on the PLC
1.
Set the IP Address of the PLC Ethernet Unit (hardware or software setting) and Node Address
(rotary switch setting).
For instance, set values as follows:
IP Address: 192.168.0.6
Network Address: 1
Node Address: 6
Note: Refer to the Chapter 9 Ethernet Connection- Setting an Ethernet Unit in the Tutorial Manual for details on
settings.
2.
Set the Node Address and Network Address of the PLC Controller Link Unit.
For instance, set values as follows:
Node Address: 4
Network Address: 3
Note: Refer to Controller Link Units Operation Manual (W309) for details on settings.
3.
Create the following routing table using CX-Net in CX-Programmer Ver. 3.1 or later and transfer it
to the PLC.
Ethernet Unit
Controller Link Unit
Screen Data
Communication method
between computer and
PLC: Ethernet
Ethernet Unit Setting
IP Address
192.168.0.6
Local Network
1
Address
6 (rotary
Node Address
switch)
1 (rotary
Unit No.
switch)
Routing Table Setting
Local Network Table
Unit No.
1 (Unit No. of the
Ethernet Unit)
2 (Unit No. of the
Controller Link Unit)
Unit Number
1
2
10-49
10-3 Data Transfer Using SPMA
Communication method between PT
and PLC: Controller Link
Controller Link Unit Setting
Network Address for
3
Controller Link
Communications
Node Address
4
Unit Address
2
Local Network
Address
1
3
Local Network Address
1
3
PT
PT Setting
Network Address
3
Controller Link Unit
5
Node Address