Wiring Example For 1:1 Connections - Omron CJ2 CPU UNIT User Manual

Cj2 cpu unit hardware
Hide thumbs Also See for CJ2 CPU UNIT:
Table of Contents

Advertisement

Connection Examples
Examples for 2-wire and 4-wire Transmission Paths
The transmission path for 2-wire and 4-wire connections are different, as shown below.
Example for 4-wire Connections
2-wire/4-wire
switch (DPDT)
Option Board
Precautions for Correct Use
Precautions for Correct Use
• All nodes must use either 2-wire connections or 4-wire connections.
• Do not use 4-wire connections with the switch on the Board set for 2-wire connections.

Wiring Example for 1:1 Connections

• Example for 2-wire Connections
CJ2M CPU Unit
RS-422A/485 Option Board
Signal
Pin
name
No.
3
SDA−
4
SDB+
1
RDA−
2
RDB+
5
FG
• Example for 4-wire Connections
CJ2M CPU Unit
RS-422A/485 Option Board
Pin
Signal
No.
name
3
SDA−
4
SDB+
1
RDA−
2
RDB+
5
FG
• Using a B500-AL001 Link Adapter
CJ2M CPU Unit
Option Board
Pin
Signal
name
No.
3
SDA−
4
SDB+
1
RDA−
2
RDB+
5
FG
CJ2 CPU Unit Hardware User's Manual
Other Unit
Other Unit
External device
Shield
External device
Shield
B500-AL001
RS-422
Signal
Signal
Pin
name
name
No.
6
RDA
RDA
RS-422
1
RDB
RDB
Interface
9
SDA
SDA
5
SDB
SDB
7
FG
FG
RDA
RDB
SDA
SDB
Signal name
6
1
9
Pin No.
Example for 2-wire Connections
2-wire/4-wire
switch (DPDT)
Other Unit Other Unit
Option Board
NC (Non Connection)
Signal
name
A(−)
B(+)
FG
Signal
name
RDA
RDB
SDA
SDB
FG
External device
RS-422
Signal
Pin
name
No.
6
RDA
1
RDB
9
SDA
5
SDB
7
FG
FG
5
7
External device
Signal
RS-422
name
RDA
RDB
SDA
SDB
FG
Appendices
A-137

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents