Table 18: General Connectivity Settings for Active Front End (continued)
Menu index
2.9.8.6
2.9.8.7
Table 19: Event Descriptions for Active Front End
Value
Info
Warning
Fault
Fault, open MCB
34
| Danfoss Drives Oy © 2024.04
Parameter
Parameter number
Fieldbus Watchdog
5245
Delay
Fieldbus Watchdog
5246
Start Delay
Description
The event is logged in the event log.
The drive issues a warning.
A fault is issued, and the modulation is stopped
A fault is issued, the modulation is stopped, and the MCB is opened, if controlled by the converter.
Value
Description
0.00–3000 s (Default:
Set a delay time for af-
5.00 s)
ter which the fieldbus
watchdog event is trig-
gered if the watchdog
bit has not changed its
value.
0.00–3000 s (Default:
Set a delay time for af-
30.00 s)
ter which the fieldbus
watchdog event is trig-
gered if the watchdog
bit has not changed its
value. This time applies
only immediately after
powering the control
unit of the drive.