Switching of loads
B.1
Connecting capacitive loads
If an F-DQ 8x24VDC/0.5A PP HF digital output module is interconnected with loads that have
an excessive capacitance, this can lead to detection of a short-circuit. Reason: The
capacitance cannot be sufficiently discharged or charged during the configured readback
time of the bit pattern test.
The typical trend shown in the diagram below represents the correlation between load
current and maximum switchable load capacitance at a supply voltage of 24 V DC.
Figure B-1
Switching of capacitive loads for the F-DQ 8x24VDC/0.5A PP HF digital output module depending on the
configured max. readback time light test / dark test.
60
Digital output module F-DQ 8x24VDC/0.5A PP HF (6ES7136-6DC00-0CA0)
Equipment Manual, 12/2022, A5E38578424-AB
B