4.2

Explanation of parameters

4.2.1

F-parameters

4.2.1.1
F-parameters
You must assign the PROFIsafe address (F-destination address together with F-source
address) to the F-module before you put it into operation.
• You define the F-source address with the "Central F-source address" parameter in the F-
CPU.
• An F-destination address unique throughout the CPU is automatically assigned for each F-
module. You can manually change the F-destination addresses assigned in the hardware
configuration.
You can find information on F-parameters for the F-monitoring time, the PROFIsafe address
assignment (F-source address, F-destination address) and the F I/O DB in the manual SIMATIC
Safety - Configuring and Programming
(https://support.industry.siemens.com/cs/ww/en/view/54110126).
See also
S7 Distributed Safety - Configuring and Programming
(https://support.industry.siemens.com/cs/ww/en/view/22099875)
4.2.1.2

Behavior after channel fault

This parameter is used to specify whether the entire F-module is passivated or just the faulty
channel(s) in the event of channel faults:
• "Passivate the entire module"
• "Passivate channel"
Digital output module F-DQ 8x24VDC/0.5A PP HF (6ES7136-6DC00-0CA0)