6.4

Value status

Properties
In addition to the diagnostics alarm and the status and error display, the F-module provides
information about the validity of each input and output signal – the value status. The value
status is entered in the process image along with the input signal.
Value status for digital input and output modules
The value status is additional binary information of a digital input or output signal. It is
entered in the process image of the inputs (PII) at the same time as the process signal. It
provides information about the validity of the input or output signal.
The value status is affected by a short-circuit and the plausibility check.
• 1
• 0
Assignment of the inputs and value status in the PII
Each channel of the F-module is assigned a value status in the process image of the inputs.
You can find the assignment in section Address space (Page 30).
Reference
A detailed description of the evaluation and processing of the respective input signals can be
found in the SIMATIC Safety – Configuring and Programming
(https://support.industry.siemens.com/cs/ww/en/view/54110126) manual.
Digital output module F-DQ 8x24VDC/0.5A PP HF (6ES7136-6DC00-0CA0)
Equipment Manual, 12/2022, A5E38578424-AB
: A valid process value is output for the channel.
B
: A fail-safe value is output for the channel, or the channel is deactivated.
B
Interrupts/diagnostic messages
6.4 Value status
53