Activated Light Test; Channel Failure Acknowledge - Siemens SIMATIC ET 200SP Equipment Manual

Digital output module f-dq 8x24vdc/0.5a pp hf
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

4.2.2.6

Activated light test

The light test is always enabled for this F-module.
4.2.2.7

Channel failure acknowledge

Use on S7-1200/1500 F-CPUs
This parameter is only relevant if the fail-safe module is operated on an S7-1500 F-CPU, and
can only be set if the F-parameter "Behavior after channel fault" is set to "Passivate channel"
and the F-parameter "Reintegration after channel fault" is set to "Adjustable".
The value of this parameter specifies how the channel should react to a channel fault:
• Manual: A channel failure is reintegrated after manual acknowledgment.
• Automatically: The channel is reintegrated automatically after a channel fault. Manual
acknowledgment is not necessary.
Use in S7-300/400 F-CPUs
The value of this parameter is not relevant in the case of operation on S7-300/400 F-CPUs.
There you set the corresponding property at the F-I/O DB by means of the ACK_NEC tag.
For detailed information about the F-I/O DB, refer to the SIMATIC Safety – Configuring and
Programming (https://support.industry.siemens.com/cs/ww/en/view/54110126) manual.
Digital output module F-DQ 8x24VDC/0.5A PP HF (6ES7136-6DC00-0CA0)
Equipment Manual, 12/2022, A5E38578424-AB