Application: Connection Of The Et 200Sp Digital Output Module F-Rq 1X24Vdc/24 - Siemens SIMATIC ET 200SP Equipment Manual

Digital output module f-dq 8x24vdc/0.5a pp hf
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Applications of the F-I/O module
5.6 Application: Connection of the ET 200SP digital output module F-RQ 1x24VDC/24..230VAC/5A (6ES7136-
6RA00-0BF0)
5.6
Application: Connection of the ET 200SP digital output module F-
RQ 1x24VDC/24..230VAC/5A (6ES7136-6RA00-0BF0)
You can use any of the 8 fail-safe digital outputs to actuate one or more digital output
modules F-RQ 1x24VDC/24..230VAC/5A.
Pay attention to the permitted current for the corresponding output channel and the total
current over all outputs at the corresponding ambient temperature.
To achieve SIL3/Cat.4/PLe see section Installation of the ground line between the power
supply and the BaseUnit (Page 32).
For operation of the digital output module F-RQ 1x24VDC/24..230VAC/5A as of FS 04, use of
the following readback times is required: Channel parameter Max. readback time light
test/dark test with the default value "0.8 / 1.0 ms".
Figure 5-6
Note
The output signals "OUT P, OUT M" of the digital output module F-RQ
1x24VDC/24..230VAC/5A are looped through from "IN P, IN M" and should therefore be
considered like the output signals of the F-DQ 8x24VDC/0.5A PP HF "DQ-PP
reason, please observe the wiring rules for the F-DQ 8x24VDC/0.5A PP HF.
The digital output module F-RQ 1x24VDC/24..230VAC/5A can no longer be shut down if a
cross circuit has developed between positive potential (e.g. L+) and DQ-PP
cross-circuits between positive potential (e.g. L+) and DQ-PP
to connect the digital output modules F-RQ 1x24VDC/24..230VAC/5A in a cross-circuit-proof
manner, e.g. as separate, sheathed cables or in separate cable ducts.
42
Wiring diagram
WARNING
Digital output module F-DQ 8x24VDC/0.5A PP HF (6ES7136-6DC00-0CA0)
Equipment Manual, 12/2022, A5E38578424-AB
, M
". For this
n
n
. To prevent
n
, you must route the lines used
n