Parameters/Address Space; Parameters - Siemens SIMATIC ET 200SP Equipment Manual

Digital output module f-dq 8x24vdc/0.5a pp hf
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Parameters/address space

4.1

Parameters

Parameters for F-DQ 8x24VDC/0.5A PP HF
Diagnostics functions should be activated or deactivated in accordance with the application,
see section Applications of the F-I/O module (Page 32).
The following parameters are possible:
Table 4- 1
Configurable parameters
Parameters
F-parameters:
Manual assignment of F-
monitoring time
F-monitoring time
F-source address
F-destination address
F-parameter signature (with-
out addresses)
Behavior after channel faults
Reintegration after channel
fault
F-I/O DB manual number
assignment
F-I/O DB number
F-I/O DB name
DQ parameters:
Digital output module F-DQ 8x24VDC/0.5A PP HF (6ES7136-6DC00-0CA0)
Equipment Manual, 12/2022, A5E38578424-AB
WARNING
Value range
Disable
Enable
1 to 65535 ms
1 to 65534
1 to 65534
0 to 65535
Passivate the entire
module
Passivate channel
Adjustable
All channels automati-
cally
All channels manually
Disable
Enable
Default
Parameter reas-
signment in RUN
Disable
No
150 ms
No
Dependent on param-
No
eter assignment of the
F-CPU
Suggested by F-
No
system
Calculated by F-
No
system
Passivate channel
No
(S7-300/400) Adjusta-
No
ble
(S7-1200/1500) All
channels manually
Disable
No
Suggested by F-
No
system
Suggested by F-
No
system
4
Scope
Module
Module
Module
Module
Module
Module
Module
Module
Module
Module
19

Advertisement

Table of Contents
loading

This manual is also suitable for:

6es7136-6dc00-0ca0

Table of Contents