High Altitude Conversion Label - Watts AERCO MLX EXT 321 Installation, Operation & Maintenance Manual

Modulating and condensing boilers
Hide thumbs Also See for AERCO MLX EXT 321:
Table of Contents

Advertisement

Modulex Light Commericial Series
CHAPTER 4: Installation Instructions
TABLE 4-7: MODULEX EXT FA (Factory) Parameters Set in PARAM HS xx Menu
Parameters
FAN MOD IGN
FAN MOD STBY
FAN MAX (FH)
FAN MIN (FL)
MAX DIFF PRO
MIN FLOW PRO
MIN FLOW RAT
BOIL HYS
BOIL SLP LIM
BOIL P VAL
BOIL I VAL
BOIL D VAL
PUMP OVERRUN
PUMP MIN MOD
CAP FLOW RATE
FAN P VAL
FAN I VAL
FAN SLP
FAN SLP POS
FAN SLP NEG
FAN START PW
FAN ADAPT
RESTARTS
SW NO
SW RWV

4.38 HIGH ALTITUDE CONVERSION LABEL

After calibration of the unit from Normal Altitude (0 - 2,000 feet) to High Altitude (2,000 –
4,500 feet) operation, the label below must be filled out with the appropriate information
and applied to the unit in close proximity to the rating label. If the unit is calibrated again
for normal altitude operation, the label should be removed.
Figure 4-42: High Altitude Conversion Label
OMM-0087_J • GF-143 • 11/17/2020
MODULEX EXT
For Low Altitude
80
26
91
31
30
00
200
5
10
25
12
00
05
----
----
04
08
----
----
----
----
----
Software N°
Software Revision
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
For High Altitude
No Change
No Change
78
No Change
No Change
No Change
No Change
No Change
No Change
No Change
No Change
No Change
No Change
----
----
No Change
No Change
----
----
----
----
----
Software N°
Software Revision
Page 80 of 150