E8 Menu Mode Operation (Door Open) - Watts AERCO MLX EXT 321 Installation, Operation & Maintenance Manual

Modulating and condensing boilers
Hide thumbs Also See for AERCO MLX EXT 321:
Table of Contents

Advertisement

Modulex Light Commericial Series
CHAPTER 5: E8 Controller and BMC Modules

E8 MENU Mode Operation (Door Open)

Opening the E8 controller hinged door reveals the E8 controls (Figure 5-4) and initiates the
MENU Mode, which enables access to an extensive set of software menus.
A
B
C
D
TABLE 5-3: E8 MENU Mode Features and Functions
ITEM
FEATURE
A
LCD display
Mounting Key
B
Access Holes
C
Change LED
Optical
D
Adaptor
E
Program Key
Manual/
F
Automatic
Switch
G
Rotary Knob
OMM-0087_J • GF-143 • 11/17/2020
INSTALLATION
E
F
Figure 5-4: E8 MENU Mode Display Features
Selected Menu/Sub-menus, parameter names/values, and selected
busses are indicated in the LCD display when in MENU Mode.
Insert narrow screwdriver deep into holes and lift up controller to
remove.
When lit, this LED indicates that the value shown in the display can
be changed using the Rotary Knob (A).
For PC connection
Used to select a sub-menu level, select a parameter value to
change, or save a new parameter value.
A 2-position (10/2 o'clock) screwdriver adjustable switch. Normally,
this switch is set to the Automatic (2 o'clock) position to allow
program control of the boiler. When set to the Manual (10 o'clock)
position, a flashing "EMERG – MODE" message is displayed.
Heating Circuit 1 (HC1) pump and the first burner stage are switched
on. Pumps for Heating Circuit 2 (HC2) and Domestic Hot Water
(DHW) will also be switched on if sensors are installed and enabled.
The pump(s) will turn off when the flow temperature reaches the
value set for MAX T-FLOW (in EXPERT/HEAT CIRCUIT 1 menu).
The first burner stage will cut off when the boiler temperature
reaches the value set for MAX T-MODUL (in
EXPERT/INSTALLATION menu).
Used to navigate through menus and parameters or adjust
parameters.
Technical Support • (800) 526-0288 • Mon-Fri, 8 am - 5 pm EST
FUNCTION
B
G
Page 88 of 150

Advertisement

Table of Contents
loading

Table of Contents